SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 9

COMMON VENT SYSTEMS

If an existing boiler/water heater is removed from a
common venting system, the common venting system
may then be too large for the proper venting of the
remaining appliances connected to it. At the time of
removal of an existing boiler/water heater, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining
connected to the common venting system are not in
operation.

Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’évacuation
commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonction-
nent pas: système d’évacuation

a) Seal any unused openings in the common venting

system.

Sceller toutes les ouvertures non utilisées du sys-
tème d’évacuation.

b) Visually inspect the venting system for proper size

and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.

Inspecter de façon visuelle le système d’évacu-ation
pour déterminer la grosser et l’inclinaison
horizontale qui conviennent et s’assurer que le
système est exempt d’obstruction, d’étranglement
de fruite, de corrosion et autres défaillances qui
pourraient présenter des risques.

c)

Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and
bathroom exhaust, so they will operate at maximum
speed. Do not operate a summer exhaust fan for a
boiler installation. Close fireplace dampers.

Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés du système d’évacuation sont installés et
les autres espaces du bâtiment. Mettre en marche
les sécheuses, tous les appareils non raccordés au
système d’évacuation commun et tous les
ventilateurs d’extraction comme les hottes de
cuisinère et les ventilateurs des salles de bain.
S’assurer que ces ventilateurs fonctionnent à la

vitesse maximale. Ne pas faire fonctionner les
ventilateurs d’été. Fermer les registres des
cheminées.

d) Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.

Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de
façon que l’appareil fonctionne de façon continue.

e) Test for spillage at the draft hood relief opening after

5 minutes of main burner operation. Use the flame
of a match or candle, or smoke from a cigarette,
cigar or pipe.

Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à
l'ouverture de décharge. Utiliser la flamme d'une
allunette ou d'une chandelle ou la fumée d'une
cigarette, d'un cigare ou d'une pipe.

f)

After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their
previous condition of use.

Une fois qu’il a été d éterminé, selon la métode
indiquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre de façor
adéquate.  Remettre les portes et les fenêtres, les
ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.

g) Any improper operation of the common venting

system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part 11 in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and or CAN/CGA-B149 Installation
Codes.

Tout mauvais fonctionnement du systéme d'évacu-
tion commun devrait étré corrigé de façor que
l'installation soit conforme au National Fue Gas
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d'installation CSA-B149. Si la grosseur d'une section
du système d'évacuation doit étré modifiée, le
système devrait étré modifié pour respecter les
valeurs minimales des tableaux pertinents de
l'appendice F du National Fuel Gas Code, ANSI
Z223.1/NFPA 54 et (ou) des codes d'installation
CSA-B149.

Содержание 8800 Series

Страница 1: ...e or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch...

Страница 2: ...8800 and 8900 finned copper heating boiler water heater pool heater To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instru...

Страница 3: ...imum site will be level central to the piping system close to a chimney and have adequate fresh air for combustion Ensure that the boiler water heater is level from front to back and from side to side...

Страница 4: ...a confined space minimum clearances listed in Table 1 or 1A must be maintained between the boiler water heater and any combustible construction When installed in a confined space Figures 1 2 3 4 and 5...

Страница 5: ...he free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of...

Страница 6: ...age 6 Figure 2 Vertical Venting Using A Masonary Chimney And Inside Air 8900 8800 Series Figure 3 Dual Flue Outlets And Inside Air 8900 8800 Series 10 FT 3 1 m 3 FT 1 m 5 FT 1 52 m 3 FT 1 m 10 FT 3 4...

Страница 7: ...0FT 3 1 m 3 FT 1 m 5 FT 1 52 m PITCH PIPE DOWN TOWARDS TERMINAL CAP 1 4 IN PER FOOT 20MM M OF RUN TO ALLOW FOR CONDENSATE DRAINAGE BUILDING OVERHANG 4 FT 1 2 M MAX 3 FT 9 m 1 5 FT 0 5m MINIMUM DISTANC...

Страница 8: ...large enough to safely vent the combined output of all the appliances WARNING If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney f...

Страница 9: ...ord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse ma...

Страница 10: ...ly piping adjacent to the boiler outlet connection CAUTION Failure to properly install the flow switch may result in damage to the boiler water heater heat exchanger voiding the warranty HEATING SYSTE...

Страница 11: ...ow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa 4 0 4 3 4 7 5 0...

Страница 12: ...ow Return Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary secondary piping system with a bypass and...

Страница 13: ...erature slowly close valve A to adjust to lower desired temperature above Temp Min 4 Check after system operating temperature has stabilized Make final adjustments 5 Follow same adjustment procedure f...

Страница 14: ...e diameter must be sized large enough to handle maximum flow through all units NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Boiler pump sized to boile...

Страница 15: ...tion of the pump size and temperature rise A cupro nickel heat exchanger may also be required The manufacturer should be consulted when these water conditions are encountered See Table 7A CAUTION The...

Страница 16: ...elow can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exch...

Страница 17: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17 Table 7B 8900 Pumping Performance RequirementTable...

Страница 18: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 18 Table 7B 8800 Pumping Performance RequirementTable...

Страница 19: ...rformance Table before making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Co...

Страница 20: ...type of gas available at the installation site call the nearest RBI representative to resolve the problem NOTE A minimum gas supply presssure of 6 in 152 mm W C natural or 11 in 279 mm W C propane and...

Страница 21: ...diagram supplied with the boiler water heater for proper wiring connections GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attem...

Страница 22: ...n interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez r...

Страница 23: ...reil ne se met pas en marche suivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fournisseur de gaz inches W C mm W C Natural 3 5...

Страница 24: ...screw cap and manifold pressure tap plug CAUTION Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur PROPANE GAS Optimum results are obtained when t...

Страница 25: ...water is 130 F 54 C The operating control should be set to the lowest setting that will satisfy the consumer s needs WARNING Setting the thermostat or operation control too high can result in scaldin...

Страница 26: ...at exchanger and burner tray components for sign of corrosion and or deterioration 4 Clean or replace components as required CAUTION Improper burner servicing can result in premature burner failure vo...

Страница 27: ...ter cutoff operate properly If not replace them 3 The flow switch contacts must be open when water flow is not present 4 The relief valve should not weep or discharge water at normal system pressure I...

Страница 28: ...ose or broken wire between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused...

Страница 29: ...f valve is properly sized for the system never exceed 160 psi Expansion tank is waterlogged Ensure expansion tank is properly sized for the system Expansion tank is isolated Ensure valve between expan...

Страница 30: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 30 PARTS LIST MODELS 420 1900 36 33...

Страница 31: ...t 03 0113 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RH Lower Front Corner Post 03 0114 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 24 Jacket End Panels Upper Lower 72 0016 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6 Inlet Outlet Header...

Страница 32: ...17 19 21 23 25 27 29 31 33 35 Burner Tube w Bracket 70 0635 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Burner Spacers 70 0363 1 70 0364 1 70 0365 1 70 0366 1 70 0367 1 70 0368 1 70 0369 1 70 0370 1 70 0371 1 7...

Страница 33: ...1 1 1 1 Main Gas Valve V4944B 1 1 2 120V 11 0168 1 1 17 A Valve 1 11 0465 1 1 1 1 1 1 A Valve 1 1 4 11 0466 1 1 1 1 1 1 1 A Valve 1 1 2 11 0467 1 1 NS Bracket Refractory Upper End 03 0306 2 2 2 2 2 2...

Страница 34: ...70 0189 1 70 0190 1 70 0191 1 NS Upper Rear Refractory Channel 70 0162 1 70 0163 1 70 0164 1 70 0165 1 70 0166 1 70 0167 1 70 0168 1 70 0169 1 70 0170 1 70 0171 1 70 0172 1 70 0173 1 70 0174 1 70 0175...

Страница 35: ...0057 1 27 Jacket Top Panel 03 0001 1 03 0002 1 03 0003 1 03 0004 1 03 0005 1 03 0006 1 03 0007 1 03 0008 1 03 0009 1 03 0010 1 03 0011 1 03 0012 1 03 0013 1 03 0014 1 03 0015 1 27a Jacket Top Panel Du...

Страница 36: ...1 70 0086 1 NS Heat Exchanger Assembly Cupronickel 70 0087 1 70 0088 1 70 0089 1 70 0090 1 70 0091 1 70 0092 1 70 0093 1 70 0094 1 70 0095 1 70 0096 1 70 0097 1 70 0098 1 70 0099 1 70 0100 1 70 0101...

Страница 37: ...1 1 1 1 1 1 1 Solenoid Valve w Regulator LP 120V 11 0374 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Pilot Valve H91WG 24V prior to 0905 11 0017 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Pilot Valve V4046C 120V prior to 09...

Страница 38: ...30 32 34 36 Orifice 47 LP 10 0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 49 2 000 3 999 LP 10 0010 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 51 4 000 5 999 LP 10 0099 8 10 12 14...

Страница 39: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39 PARTS LIST MODELS 2000 4000 22 7 36 33 30 8 6 39 42 18 21 25 19...

Страница 40: ...n Headers 57 0226 24 24 24 24 24 24 NS Nut Inlet Outlet Return Headers 57 0492 24 24 24 24 24 24 NS Heat Exchanger V Baffle 03 1147 15 03 1148 30 03 1149 30 03 1150 30 03 1151 30 03 1152 30 12 Base Fr...

Страница 41: ...2 FM Only 11 0455 1 1 18 End Refractory Panel Left Right 05 0050 2 2 2 2 2 2 19 Center Refractory Panel 853413 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4...

Страница 42: ...0V 70 9014 1 1 1 1 1 1 Ignitor PSE NA29 LP 24V 70 0631 1 1 1 1 1 1 Ignitor PSE NA185 LP 120V 70 0632 1 1 1 1 1 1 33 Solenoid Valve w Regulator NG 24V 11 0373 1 1 1 1 1 1 Solenoid Valve w Regulator LP...

Страница 43: ...28 32 36 40 Orifice 19 2 000 3 999 NG 10 0007 20 24 28 32 36 40 Orifice 22 4 000 5 999 NG 10 0095 20 24 28 32 36 40 Orifice 25 6 000 7 999 NG 10 0097 20 24 28 32 36 40 Orifice 34 LP 10 0021 20 24 28...

Страница 44: ...the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next ad...

Страница 45: ...led instructions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREME...

Страница 46: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 46...

Страница 47: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 47...

Страница 48: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Отзывы: