![RayTek RAYCMLTJM Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/raytek/raycmltjm/raycmltjm_operating-instructions-manual_3970115029.webp)
Programming
29
Rev. B 06/2011
CM
8
Programming
8.1
General Command Structure
Requesting a parameter
?E<CR>
“?“ is the command for “Request“
“E“ is the parameter requested
<CR> (carriage return, 0D
h
) is closing the request.
Remark
: It is possible to close with <CR> <LF> (0D
h
0A
h
), but
<LF> (0A
h
) is not necessary.
Setting a parameter (Poll Mode)
The parameter will be stored into the device flash memory.
E=0.975<CR> “E“ is the parameter to be set
“=“ is the command for “set a parameter“
“0.975“ is the value for the parameter
<CR> (carriage return, 0Dh) is closing the request
Remark
: It is possible to close with <CR> <LF> (0D
h
0A
h
), but
<LF> (0A
h
) is not necessary.
Setting a parameter without writing it into the device flash memory.
This function is for test purposes only.
E#0.975<CR> “E“ is the parameter to be set
“#“ is the command for “set parameter without writing it into
the Flash“
“0.975“ is the value for the parameter
<CR> (carriage return, 0Dh) is closing the request.
Remark
: It is possible to close with <CR> <LF> (0D
h
0A
h
), but
<LF> (0A
h
) is not necessary.
Device response format:
!E0.975<CR><LF> “!“ is the parameter for “Answer“
“E“ is the Parameter
“0.975“ is the value for the parameter