Equipment Base
The heater should be mounted on a level, structurally
sound surface. The heater is approved for installa-
tion on a combustible surface but must NEVER be
installed on carpeting. Gas-fueled equipment installed
in enclosed parking garages must be located at least
18 in. above the floor.
In addition, the heater shall be installed such that the
gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance
operation or service (circulator replacement, control
replacement, etc.).
If the heater needs to be secured to the ground, use
the hole pattern shown in Fig. 5, following local codes.
Clearances
Indoor Installations
9
Heater Side
Minimum Clearance
from Combustible
Surfaces
Minimum
Service
Clearance
Floor*
0"
0"
Rear
12"
36"
Right Side
1"
24"
Left Side
1"
1"
Top
0"
10"
Front
Open
30"
Vent
1"
1"
* DO NOT install on carpeting
Table C: Clearances – Indoor Installations
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations
CAUTION:
This heater should be located in an area
where water leakage will not result in damage to the
area adjacent to the appliances or to the structure.
When such locations cannot be avoided, it is
recommended that a suitable catch pan, adequately
drained, be installed under the appliance. The pan
must not restrict air flow.
Top View
Front View
Содержание XTherm 2505
Страница 2: ...2 Rev 2 reflects the following Changes to Additions Deletions ...
Страница 46: ...WIRING DIAGRAM Models 2505 4005 46 For a full size drawing visit www raypak com commercial wiring_diagrams ...
Страница 61: ...61 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 ...
Страница 65: ...65 ...
Страница 66: ...66 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...