40
Use the
MENU
button to open the menu options, select
the
ADJUST
menu, go to System Settings page. Once
in the system settings screen use the Setpoint item.
Adjust the setpoint using the
UP
and
DOWN
arrow.
After making the setpoint selection press SET button
to apply the changes (a confirmation bar will turn
green showing that value has been applied). Minimum
setpoint is 50ºF; maximum is 220ºF for H models,
150ºF for WH models and 104ºF for P models. The
default setpoint is 180ºF for H models, 125ºF for WH
models and 80ºF for P models.
View Menu
The
VIEW
menu (See Table P) is the default menu.
It displays sensor temperatures, the modulation rate
of the blower, heater cascade status, pump operation
and CFH information. Some of the items displayed
are mode specific and are only observable when its
corresponding mode is active.
Menu - Initial Adjustment
To change settings use the
MENU
key to scroll to the
SETUP/ADJUST
menu. The
ADJUST
menu allows
the installer to make adjustments to items shown in
Table R.
Refer to the VERSA IC Control I&O Manual (Catalog
#5000.72) for detailed setup instructions.
Table R: View Menu
Item
Application
Description
OUTDOOR
H MODE 1, 2, 3
Outdoor air temperature, available when TARGET = RSET in ADJUST menu
Target
H MODE 1, 2, 3
Current target temperature, available when Target = SETP in the ADJUST menu (default), and
(EMS / MODB)
SUPPLY
H MODE 1, 2, 3
Current system supply temperature
IND Supply
H MODE 3
Current temperature being supplied to the indirect system
Boil OUTLET
All
Current boiler outlet temperature
Boil INLET
All
Current boiler inlet temperature
Boil ΔT
All
Current temperature difference between boiler outlet and boiler inlet
DHW SUPPLY
H MODE 2, 3
Current indirect DHW supply temperature, requires IND Sensor = ON in ADJUST menu
TANK
WH
Current tank temperature
P
BOILER STATUS
All
IDLE, PREP, IGN, MOD RATE %, POST, SOFT, HARD
end of the actuator motor. This will allow the motor
to rotate into alignment with the bracket.
5. Align the motor with the valve mounting bracket.
6. With the motor and bracket aligned, slide the lock
bracket forward to secure the motor to the anti-ro-
tation bracket and tighten the 7/16” hardware.
Condensate Switch
The condensate switch is located in the flue collector
of the condensing exchanger. The switch will shut the
unit down in the event of a blockage in the condensate
management system.
User Interface
The Touch Screen (TS) user interface uses a high
definition 7” capacitive screen. It includes an exten-
sive graphical library used to represent different pipe
configurations, error location, and operation of the unit.
The TS has the same basic menu distribution as the
original LCD Display, when pressing the
MENU
button
the menu bar becomes visible at the bottom of the
screen allowing navigation through four addition sub
menus (
VIEW
,
ADJUST
,
BOILER
, and
TOOLS
).
For detailed descriptions of the various screens, page
flows and basic instructions, consult the Touch Screen
Quick Start User Guide (Catalog #5000.74) and
VERSA IC Control I&O Manual (Catalog #5000.72).
Adjusting the XTherm Setpoint
Fig. 52: User Interface
Fig. 51: Condensate Switch
Содержание XTherm 2505
Страница 2: ...2 Rev 2 reflects the following Changes to Additions Deletions ...
Страница 46: ...WIRING DIAGRAM Models 2505 4005 46 For a full size drawing visit www raypak com commercial wiring_diagrams ...
Страница 61: ...61 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 ...
Страница 65: ...65 ...
Страница 66: ...66 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...