Table S: Setup/Adjust Menu
Item
Application
Range
Description
Default
TARGET
H MODE 1, 2, 3
RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
SETP
TANK SETP
WH
OFF, 50
°
F to 150
°
F
Tank set point temperature
125
°
F
TANK DIFF
WH
2
°
F to 10
°
F
Tank Differential temperature
5
POOL SETP
P
50ºF to 104ºF, 106ºF
Pool set point temperature
80ºF
POOL DIFF
P
1ºF to 5ºF
Pool Differential temperature
2ºF
POOL MAX
P
110ºF to 120ºF
Pool Maximum temperature
110ºF
MODE
H MODE 1, 2, 3
1,2,3
Piping and application configuration.
1
SETPOINT
H MODE 1, 2, 3
50
°
F to 220
°
F
Boiler target temperature while a heat demand is present for set-
point operation
180
°
F
OUT START
H MODE 1, 2, 3
35
°
F to 85
°
F
Outdoor starting temperature - outdoor reset
70
°
F
OUT DESIGN
H MODE 1, 2, 3
-60
°
F to 45
°
F
Outdoor design temperature - outdoor reset
10
°
F
Boil START
H MODE 1, 2, 3
35
°
F to 150
°
F
Starting boiler target temperature when the outdoor temperature
is at outdoor start outdoor reset
70
°
F
Boil DESIGN
H MODE 1, 2, 3
70
°
F to 200
°
F
Design boiler target temperature when the outdoor temperature is
at outdoor design outdoor reset
180
°
F
TARGET MAX
H MODE 1, 2, 3
100
°
F to PIM value*
Maximum target system temperature
220
°
F
TARGET MIN
H MODE 1, 2, 3
OFF, 50
°
F to 190
°
F
Minimum target system temperature
50
°
F
TARGET DIFF
H MODE 1, 2, 3
2
°
F to 42
°
F
Differential for target system temperature
10
°
F
IND SENSOR
H MODE 1, 2, 3
OFF <> ON
Selects whether a DHW sensor is used for indirect DHW tank
OFF
IND SETP
H MODE 2, 3
OFF, 50
°
F to 180
°
F
Target Indirect DHW Temperature, requires IND SENSOR = ON
140
°
F
DHW DIFF
H MODE 2, 3
2
°
F to 10
°
F
Differential for the target indirect DHW tank temperature, requires
IND SENSOR = ON
6
°
F
IND SUPPLY
H MODE 2, 3
OFF, 50
°
F to PIM value*
Target boiler temperature for the DHW heat exchanger during
indirect DHW operation, requires IND SENSOR = OFF
180
°
F
DHW PRIORITY
H MODE 2
OFF <> ON
Selects whether or not Indirect DHW priority is active during indi-
rect DHW operation
OFF
PRI OVR
H MODE 2, 3
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority override time
1:00hr
SYS PURGE
All
OFF, 0:20min to 20:00min
Sets the length of the system pump post purge
20 seconds
MIX TYPE
H / WH / P MIX
H (VALVE, PUMP, PLNT)
WH (1 <> 2)
Selects the type of control depending on pipe configuration for
CWP
H VALVE
WH 2
MIX TARGET
H / WH / P MIX
50
°
F to 140
°
F
Inlet Target Temperature
120
°
F
MIX LOCK
H / WH / P MIX
OFF <> ON
The equipment will trigger a warning when “MIX Target” is not
reached within 7 minutes. MIX LOCK = ON; Alarm and lockout,
MIX LOCK = OFF; Alarm only
OFF
MIX TRIM
H / WH / P MIX
-5 to 5
This adjustment is for various types and sizes of units as well as
various actuator motor speeds and types supplied by Raypak
0
MIX SPEED
H / WH / P MIX
SLOW <> MED <> FAST
This setting defines speed of response.
MED
MIX INV
H / WH / P MIX
OFF <> ON
This option is related to the use of spring return actuators with a
proportional valve
OFF
WWSD
H MODE 1, 2, 3
40
°
F to 100
°
F
The system warm weather shutdown temperature outdoor reset,
requires TARGET = RSET
70
°
F
UNITS
All
deg F <> deg C
Show units using icons in display
deg F
MODBUS
All
OFF <> MNTR <>
TEMP <> RATE
ModBus Operating Mode: Off, Monitor, Temp Control, Rate
Control
MNTR
ADDRESS
All
1 to 247
ModBus slave address
1
DATA TYPE
All
RTU <> ASCI
Modbus data type
RTU
BAUD RATE
All
2400 <> 9600 <> 19K2 <>
57K6 <> 115K
19K2
PARITY
All
NONE <> EVEN <> ODD
EVEN
* Maximum operator dial setting.
Содержание XTherm 2505
Страница 2: ...2 Rev 2 reflects the following Changes to Additions Deletions ...
Страница 46: ...WIRING DIAGRAM Models 2505 4005 46 For a full size drawing visit www raypak com commercial wiring_diagrams ...
Страница 61: ...61 ...
Страница 62: ...62 ...
Страница 63: ...63 ...
Страница 64: ...64 ...
Страница 65: ...65 ...
Страница 66: ...66 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...