Table F: Boiler Temperatures and Minimum Pipe Size at Varying Return Temperatures
System
Return Temp
Supply Temp
1
Supply Temp
1
Supply Temp
1
(°F)
(°F)
<80' equiv. 80-200' equiv.
(°F)
<80' equiv. 80-200' equiv.
(°F)
<80' equiv. 80-200' equiv.
60
138
2"NPT
2 1/2"NPT
147
2"NPT
2 1/2"NPT
154
2"NPT
2 1/2"NPT
80
138
2"NPT
2 1/2"NPT
147
2"NPT
2 1/2"NPT
154
2 1/2"NPT
3"NPT
100
138
2 1/2"NPT
3"NPT
147
2 1/2"NPT
3"NPT
154
2 1/2"NPT
3"NPT
120
145
2 1/2"NPT
3"NPT
158
2 1/2"NPT
3"NPT
170
2 1/2"NPT
3"NPT
140
165
2 1/2"NPT
3"NPT
178
2 1/2"NPT
3"NPT
190
2 1/2"NPT
3"NPT
160
185
2 1/2"NPT
3"NPT
198
2 1/2"NPT
3"NPT
210
2 1/2"NPT
3"NPT
1
-Approximate high fire heater outlet temperature based on the standard heater pump and the recommended connecting pipe size.
Model 1005
Minimum Pipe Size
2
Model 1505
Minimum Pipe Size
2
Model 2005
Minimum Pipe Size
2
2
-Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater.
Fig. 14: Single Heater with Primary/Secondary Piping
Fig. 15: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
Fig. 16: Single Domestic Hot Water Heater and Storage
Tank
16
Domestic Hot Water
When designing the hot water piping system for
domestic hot water applications, water hardness
should be considered. See Table H on page 18 for the
required tubing sizes and expected supply tempera-
tures for different operating conditions. Water
hardness is expressed in grains per gallon.
Fitting Type
Equivalent Length (ft)
2-1/2” NPT
3” NPT
90° Elbow (Std.)
8.5
9.4
90° Elbow (Long rad.)
3.5
3.6
45° Elbow
3.0
3.4
Gate Valve (Full open)
1.6
1.6
Swing Check Valve
22
25
Table G: Equivalent Lengths of Pipe for Typical Fittings
Note: Equivalent lengths are calculated based on typical operating
conditions with typical Schedule 40 pipe fittings and valves.
Equivalent lengths are approximate and may vary greatly.
*Maximum 4 times the pipe diameter or 12”, whichever is less.