44
Glycol % Setting
The XFiire product is equipped with algorithms that will
ensure optimum operation when using different glycol
concentrations as the heat media. From the VERSA IC
touchscreen, the user must select a glycol concentration.
This setting can be found within the Adjust Menu within
System Settings.
NOTE:
The factory default value is 50% glycol
concentration. Restoring factory defaults WILL NOT
reset this value.
When replacing the VERSA IC, it is important to update
the glycol percentage value as needed for proper system
operation.
The glycol protection will reduce the maximum firing rate,
but will also change the entire heating profile depending on
the model size. See
Figure 44
.
Figure 44. Glycol Operation Chart
Vent Protection
The XFiire heaters are equipped with a vent temperature
sensor located at the rear of the heater. See
Figure 4.
The vent protection algorithm will anticipate a flue
temperature overshoot and adjust the firing rate of the
heater to prevent excessive flue temperatures from
occurring.
NOTE:
The factory default is set to “PVC”.
During commissioning of the heater, the vent material
must be selected in the Adjust Menu (Submenu of System
Settings) to indicate the vent material installed on the
heater.
The settings for the Vent Protection include:
NOTE:
Use only certified vent material ANSI/ASTM
D1785 Sch 40 PVC, ANSI ASTM F441 Sch 40 CPVC.
• Vent Material.
PVC (149°F/65°C),
CPVC (194°F/90°C),
PPS (Polypropylene) (230°F/110°C),
Stainless Steel (AL29-4C)
• Vent Differential.
Subtractive value from max vent
temperature that defines when the control will take
action to prevent unit from reaching the max vent
temperature. Default 10°F (5.6°C) selectable from
1°F (0.6°C) - 20°F (11°C).
• Vent Rate.
This value defines the max firing rate
the heater will be allowed to operate at when Vent
Protection is active.
If the vent temperature exceeds the allowable limit for
the vent material selected, the burner will cycle. This
is an automatic reset function and as soon as the vent
temperature drops to an acceptable level, the heater will
return to normal operation.
NOTE:
The use of PVC/CPVC will require the user to
limit the maximum setpoint of the heater in the Adjust
menu.