23
For Standing Pilot Model with
Robertshaw Gas Valve, On/Off
Operation
1. STOP! Read the safety information above.
2. Set the tankstat on the lowest setting.
3. Turn OFF all electric power to the heater.
4. Remove heater door panel.
5. Push in gas control knob slightly and turn clock-
wise to
"OFF".
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If your smell
gas, STOP! Follow "B" in the safety information
above on this label. If you don't smell gas, go to
the next step.
7. Locate pilot mounted on the right side of the burn-
er drawer, right of first burner.
8. Turn knob on gas control counter-clockwise
to "Pilot".
GAS CONTROL
KNOB SHOWN
IN "OFF" POSITION
GAS INLET
Fig. 20: Robertshaw Gas Valve
NOTE:
Knob cannot be turned from "PILOT" to
"OFF" unless knob is pushed in slightly. Do not force.
HONEYWELL PILOT
ROBERTSHAW PILOT
Fig. 21: Honeywell and Robertshaw Pilots
9. Push in control knob all the way and hold in,
immediately light the pilot with a match. Continue
to hold control knob in for about one minute after
the pilot is lighted, release knob and it will pop
back up. Pilot should remain lighted. If it goes out,
repeat steps 4 through 8.
*
If knob does not pop up when released, stop
and immediately call your service technician
or gas supplier.
*
If the pilot does not stay lit after several tries,
turn the gas control knob to "OFF" and call
your service technician or gas supplier.
10. Stand to the side of the heater and turn the gas
control knob counter-clockwise
to "ON".
11. Replace heater door.
12. Turn "ON" all electrical power to the heater.
13. Set the tankstat to the desired setting.
For Standing Pilot Model with
Honeywell Gas Valve, On/Off
Operation
1. STOP! Read the safety information.
2. Set the tankstat to the lowest setting.
3. Turn Off all electrical power to the heater.
4. Remove heater door panel.
5. Turn gas control knob clockwise
to "OFF".
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, STOP! Follow "B" in the safety information
above on this label. If you don't smell gas, go to
the next step.
7. Locate pilot mounted on the right side of the burn-
er drawer, right of first burner.
8. Turn knob on gas control counter-clockwise
to "PILOT".
9. Push down and hold the red reset button in, imme-
diately light the pilot with a match. Continue to hold
down red reset button for about one minute after
the pilot is lighted. Release red reset button and it
will pop back up. Pilot should remain lighted. If it
goes out, repeat steps 4 through 8.
GAS CONTROL
KNOB SHOWN
IN "OFF"
POSITION
GAS INLET
Fig. 22: Honeywell Gas Valve
Содержание 2600401
Страница 17: ...17 Wiring Diagrams Fig 15 Standing Pilot Model 0260 FIELD INSTALLED...
Страница 18: ...18 Fig 16 Intermittent Ignition Device IID Model 0260...
Страница 19: ...19 Fig 17 Intermittent Ignition Device IID Models 0330 0400...
Страница 20: ...20 Fig 18 Intermittent Ignition Device IID Model 0261 Low NOx...
Страница 21: ...21 Fig 19 Intermittent Ignition Device IID Models 0331 0401 Low NOx...
Страница 37: ...37...
Страница 38: ...38...
Страница 39: ...39...
Страница 40: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...