22
SERVICING
PROCEDURES
Sequence of Operation
Intermittent Ignition Device (IID)
Heaters equipped with the IID system will automatical-
ly light the pilot burner first and then the main burner,
each time there is a call for heat from the tankstat.
Whenever the tankstat calling for heat, the circulator
supplied with the heater, will be energized and should
be running.
The ignition control module will also be energized to
initiate the pilot ignition by opening the first main valve
(pilot). At the same time, the electronic spark genera-
tor in the module produces a high voltage spark pulse
output that lights the pilot burner. If the pilot burner
does not light, the module will not energize the second
main valve and the burners will not light. Ignition spark
continues only until the timed trial for ignition period
ends.
Then, the module goes into safety shutdown or lock-
out. Lockout de-energizes the first main valve operator
and closes the first main (pilot) valve in the gas con-
trol, stopping pilot gas flow. The ignition control system
must be reset by setting the tankstat below water tem-
perature for one minute or by turning off power to the
module for one minute.
When the pilot flame is established, flame rectification
circuit is completed between the sensor and burner
ground. The flame sensing circuit in the module
detects the flame current, shuts off the spark genera-
tor and energizes the second main valve operator
which opens the second main valve. This allows gas to
flow to the burners where it is ignited by the pilot burn-
er flame.
When the tankstat is satisfied, the valve operators are
de-energized shutting off the pilot and main burners,
and also the circulator.
Start-up Procedures
Filling the System
Fill system with water. Purge all air from the system
using purge valve sequence. After system is purged of
air, lower system pressure. Flush system before put-
ting into operation to ensure that foreign material does
not damage pump seals.
Checking the Circulator
Before lighting the heater and after system is filled,
make sure that circulator is operating properly. Manual
gas valve should be off.
Lighting the Heater
For your safety read carefully before proceeding to
light the heater.
For Standing Pilot Models
A. This heater has a pilot which must be lighted by
hand. When lighting the pilot, follow these instruc-
tions exactly.
B. BEFORE LIGHTING smell all around the heater
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will set-
tle on the floor.
WHAT TO DO IF YOU SMELL GAS
•
Do not try to light any appliance.
•
Do not touch any electric switch.
•
Do not use any phone in your building.
•
Immediately call your gas supplier from a neigh-
bor's telephone. Follow the gas supplier's
instructions.
•
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in, move or turn the
gas control knob or lever. Never use tools. If the
knob or lever will not push in, move or turn by
hand, don't try to repair it, call a qualified service
technician. Force or attempted repair may result in
a fire or explosion.
D. Do not use this heater if any part has been under
water. Immediately call a qualified service techni-
cian to inspect the heater and to replace any part
of the control system and any gas control which
has been under water.
NOTE:
Circulator motor supplied with the heater
does not require lubrication.
WARNING:
If you do not follow these instructions
exactly, a fire or explosion may result causing prop-
erty damage, personal injury or loss of life.
CAUTION:
Propane gas is heavier than air and
sinks to the ground. Exercise extreme care in light-
ing heater in confined areas.
Содержание 2600401
Страница 17: ...17 Wiring Diagrams Fig 15 Standing Pilot Model 0260 FIELD INSTALLED...
Страница 18: ...18 Fig 16 Intermittent Ignition Device IID Model 0260...
Страница 19: ...19 Fig 17 Intermittent Ignition Device IID Models 0330 0400...
Страница 20: ...20 Fig 18 Intermittent Ignition Device IID Model 0261 Low NOx...
Страница 21: ...21 Fig 19 Intermittent Ignition Device IID Models 0331 0401 Low NOx...
Страница 37: ...37...
Страница 38: ...38...
Страница 39: ...39...
Страница 40: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...