User Guide of RFL- RFL-C4000S
13
3.2
Output Head and Installation
Figure 3 Dimensions of iQB Output Head
The QBH and iQB laser output head of RFL-C4000S are all the standard QBH interface. The
specific appearance and dimensions are shown in Figure 3 above.
CAUTIONS:
◆
Inspect the output lens before installing the output head to the
processing head. Clean the output lens if necessary.
◆
It is strictly prohibited to disassemble the output head by personnel not
approved by Raycus, or the warranty is void.
3.3
Cooling Requirements
Table 6 Cooling Requirements
Model
RFL-C4000S
Cooling Capability(W)
>10000
Minimum Flow(L/min)
40
Maximum Pressure(Bar)
7
Pipe Inner Diameter(mm)
25
Water temperature of coolingsystem (
℃
)
22
±
1
℃
(1)
The water temperature setting of cooling system:
22
±
1
℃(
RFL-C4000S
)
(2)
Cooling system filter access requirements: