4.3.3 “OTHER ALARMS CONFIG...” Sub-Menu
This sub-menu allows the user to set up all alarms that do not directly relate to the temperature
sensors. These include all AC alarms (voltage, current. ground fault, etc.) as well as protection
settings such as power limiting, etc.
Each alarm may be ENAbled or DISabled. If the alarm is ENAbled, an alarm setting and filter
setting may be entered.
CONTROL SETPOINT
=
20°C
LO TS 1
=
-10°C
LO LOAD
=
1.0 A
HI GFI
=
50 mA
GFI TRIP
=
75 mA
TS ALARMS CONFIG...
OTHER ALARMS CONFIG...
POINT SETUP...
COMMON SETUP...
COMMUNICATIONS
SETUP...
--- END ---
Other Alarms Configuration Sub-Menu
LO LOAD
=
{ENA or DIS}
LO LOAD
=
{0.3 to 100.0} A
LO LOAD FILTER
=
{0 to 12} S
HI LOAD
=
{ENA or DIS}
HI LOAD
=
{0.3 to 100.0} A
HI LOAD FILTER
=
{0 to 12) S
HI GFI
=
{ENA or DIS}
HI GFI
=
{20 to 250} mA
HI GFI FILTER
=
{0 to 12} S
GFI TRIP
=
{ENA or DIS}
GFI TRIP
=
{20 to 250} mA
* LO VOLT
=
{ENA or DIS}
* LO VOLT
=
{10 to 330} V
* LO VOLT FILTER
=
{0 to 12} S
* HI VOLT
=
{ENA or DIS}
* HI VOLT
=
{10 to 330} V
* HI VOLT FILTER
=
{0 to 12} S
LO RESIST
=
{ENA or DIS}
LO RESIST
=
{1 to 100} %
LO RESIST FILTER
=
{0 to 12} S
HI RESIST
=
{ENA or DIS}
HI RESIST
=
{1 to 250} %
HI RESIST FILTER
=
{0 to 12} S
NOMINAL RESIST
=
{2.00 to 2000.00}Ω
(only if LO or HI is enabled)
OVERCURRENT TRIP
=
{ENA or DIS}
(only if SSR is being used)
SWITCH FAIL
=
{ENA or DIS}
HTC RESET
=
{ENA or DIS}
C.B. LIMITING
=
{ENA or DIS}
(only if SSR is being used)
POWER LIMITING
=
{ENA or DIS}
(only if SSR is being used)
SWITCH LIMITING
=
{ENA or DIS}
(only if SSR is being used)
CONTACTOR COUNT
=
{ENA or DIS}
(only if Deadband or Prop. Amb.
Contactor are being used)
CONTACTOR COUNT
=
{0 to 999,999}
(only if Deadband or Prop. Amb.
Contactor are being used)
EEROM DATA FAIL
=
{ENA or DIS}
--- END ---
• Only if VOLT SOURCE is set to the point being used.