4.3 CONFIGURE MODE
The CONFIGURE mode is selected when the operator presses the SHIFT key followed by the
CONFIG key. This mode allows you to examine or alter the Controller’s configuration.
Menu items with a trailing “...” indicate an entry point to a sub-menu. To enter a sub-menu, use
and to position the menu item in the display and then press . Note that the controller
“remembers” where you are in the CONFIGURE mode if you temporarily switch to a different
mode (such as the MONITOR mode). Switching back to the CONFIGURE mode will return you
to the same menu item.
IMPORTANT: A few of the controller parameters that are often used have been duplicated in
the CONFIGURE mode main menu for quick access. These parameters (Lo TS 1, Lo Load, Hi
GFI, GFI Trip) may also be accessed using their respective sub-menus.
4.3.1 Main Menu
Monitor Mode Main Menu
CONTROL SETPOINT
=
{-60 to 570}°C
LO TS 1
=
{-60 to 570}°C
LO LOAD
=
{0.3 to 100.0} A
HI GFI
=
{20 to 250} mA
GFI TRIP
=
{20 to 250} mA
TS ALARMS CONFIG...
Note that the menu items with a trailing “...” indicate
the entry point to a sub-menu.
OTHER ALARMS CONFIG...
POINT SETUP...
COMMON SETUP...
COMMUNICATIONS SETUP...
LOCK DATABASE
(only if passcode is not 0 and database is unlocked)
UNLOCK DATABASE
(only if passcode is not 0 and database is locked)
--- END ---
Table 4.4
4.3.2 “TS ALARM CONFIG...” Sub-Menu
This sub-menu is used to set up alarms that relate to any of the temperature sensors. Each alarm
may be ENAbled or DISabled, and if the alarm is ENAbled, an alarm setting may be entered.
CONTROL SETPOINT
=
20°C
LO TS 1
=
-10°C
LO LOAD
=
1.0 A
HI GFI
=
50 mA
GFI TRIP
=
75 mA
TS ALARMS CONFIG...
OTHER ALARMS SETUP...
POINT SETUP...
COMMON SETUP...
COMMUNICATIONS SETUP...
--- END ---
TS Alarms Configuration Sub-Menu
TS 1 FAIL
=
{ENA or DIS}
LO TS 1
=
{ENA or DIS}
LO TS 1
=
{-60 to 570}°C
HI TS 1
=
{ENA or DIS)
HI TS 1
=
{-60 to 570}°C
TS 2 FAIL
=
{ENA or DIS)
LO TS 2
=
{ENA or DIS)
LO TS 2
=
{-60 to 570}°C
HI TS 2
=
{ENA or DIS}
HI TS 2
=
{-60 to 570}°C
LO TS FILTER
=
{0 to 999} MIN (only if LO TS 1 or 2 are enabled)
HI TS FILTER
=
{0 to 999} MIN (only if HI TS 1 or 2 are enabled)
LATCH TS ALARMS
=
{YES or NO}
CTL TS FAIL
=
{ENA or DIS}
--- END ---
Table 4.5