18
THIS APPLIANCE MUST BE CONNECTED TO A FULLY PUMPED SYSTEM.
BURNER SPECIFICATION
Burner Input
COOKER BURNER
100K
80K
60K
100K/80K/60K
(kW) Continuous Running
34.2
27.7
21.4
19.5
(kW) Cycling
N/A
N/A
N/A
4.4
(Btu’s) Continuous Running
116,760
94,600
73,000
66,875
(Btu’s) Cycling
N/A
N/A
N/A
14,950
Boiler Output
100K
80K
60K
100K/80K/60K
(kW) Continuous Running
29.3
23.5
17.6
2.1
(kW) Mean Cycling
N/A
N/A
N/A
1.2
(Btu’s) Continuous Running
100,000
80,000
60,000
7,000
(Btu’s) Mean Cycling
N/A
N/A
N/A
4,000
Nozzle
0.85 80°S (C.E.N)
0.65 80°S (C.E.N)
0.55 80°S (C.E.N)
0.5 60°S (C.E.N)
Pressure
100K
80K
60K
100K/80K/60K
(Bar)
7.4
7.4
7.1
7.1
(PSI)
107
108
103
110
Fuel Consumption
100K
80K
60K
100K/80K/60K
(L/Hr) Continuous Running
3.6
2.9
2.2
2.1
(L/Hr) Cycling
N/A
N/A
N/A
0.47
US Gal/Hr
Continuous Running
0.95
0.77
0.58
0.55
US Gal/Hr Cycling
N/A
N/A
N/A
0.12
All data are taken under laboratory conditions and may vary in use.
Differential Pressure Across the Boiler
Design flow rate through the boiler
38.2 L/min / 8.4 Gpm
Static differential across the boiler
52.4 mbar / 21” wg
Dynamic pressure differential across the boiler
33 mbar / 13.23” wg
Note: Design temperature differential across the boiler = 11°C (52°F)
The installation must comply with the current editions of the following:
•
BS 5410: Oil Installations Part 1 under 45kW.
•
The Building Regulations: Part J England, Wales,
•
Part F Section 4 Scotland, Part L Northern Ireland and Part J Ireland.
The Control of Pollution (Oil) Regulations.
•
BS 5449: Forced circulation hot water central heating systems for domestic installations.
Boiler
Cooker
Air Setting
CO2%
Air Setting
CO2%
9
11.5
5
10
8
11.8
4
10.34
7
11.9
3
10.8
6
12.2
2
11.2
Find the correct position of the air control, which gives the
highest reading of CO2 within the range of the table without
exceeding a smoke No. 0-1 (Bacharach Scale).