background image

The Rayburn is a floor standing combined cooker and
central heating boiler. It gives independent operation for
space heating, domestic hot water and cooking. 
The appliance is fired by two independent pressure jet oil
burners. Either burner can be independently operated
under programmer control if required.
The boiler is designed for use on a fully pumped low
pressure hot water circulation system, with a pumped
over run facility or alternatively on a sealed system limited
to 2 bar.

IMPORTANT

This appliance must only be used with Gas Oil to 
35 seconds to BS2869: Class D

.

An Indirect Cylinder to BS 1566: Part 1 must be 
fitted.

If the heating circuits are controlled in such a way
that both heating and cylinder circuits can be 
closed off at the same time then a PERMANENTLY
OPEN BYPASS LOOP should be provided.

A Fire Valve MUST be fitted in the oil supply line.

The supplied in line filter MUST be fitted.

This appliance must be commissioned by a competent
engineer, such as OFTEC approved or a commissioning
engineer as shown on the Rayburn list.

The installation of the appliance must be in accordance
with the relevant requirements of the current Building
Regulations BS 7671: 1992 (formerly IEE Wiring
Regulations and the bylaws of the local Water
Undertaking. It should also be in accordance with the
relevant recommendations of the following current
British Standard Codes of Practice.

BS 5410

Installation of oil fired appliances for space

heating and hot water supply purposes. Part 1 Boilers of
rated output exceeding 45 kW.

BS 5449

Central Heating for domestic purposes. Part 1,

Forced circulation hot water system.

Building Regulations England & Wales

, Part J. 

Heat producing appliances.

Building Standards Scotland

- Technical Standard Part

F. Heat producing appliances and storage of liquid and
gaseous fuel.

Building Regulations Northern Ireland

- Technical

Booklet to Part L. Heat producing appliances.

The control of Pollution (Oil) Regulations.

Appliance Hearth.

The surface temperature of the floor

below the appliance does not exceed 100

˚

C. The

constructional hearth described in Section J does not
apply. However, this appliance must be installed on a
solid floor of incombustible material which is capable of
supporting the total weight.

The location chosen for the appliance must permit the
installation and the provision of a satisfactory flue and an
adequate air supply. The location must also provide
adequate space for servicing and for air circulation around
the appliance. See ‘Installation of Appliance”.

The space in which the appliance is to be fitted must have
the following minimum dimensions:

Between wall and LH side of appliance - 3mm
Between wall and RH side of appliance - 10mm
Above the raised insulating cover handle - 60mm

In addition, adequate clearance must be available at the
front of the appliance to enable it to be operated and
serviced. Flue pipes and fitting must not be closer than
25mm to combustible materials and where passing
through a combustible partition such as ceiling or roof,
must be enclosed in a non-combustible sleeve providing
an air space of at least 25mm.

Space around the flue pipes passing through walls or
floors should be sealed against the passage of smoke and
flame, a fire stop valve must be provided where the flue
passes through a ceiling.

Where the cooker is to stand in a recess or against a wall
which is to be tiled, 

in no circumstances should the

tiles overlap the cooker top plate.

Site requirements

5

REGULATIONS

LOCATION

INTRODUCTION

Содержание Heatranger 480D

Страница 1: ...WARNING This information is a copy of an original archive therefore Aga cannot be held responsible for its continued accuracy...

Страница 2: ...O T H E R G B I E P A T E N T S P E N D I N G PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THIS APPLIANCE For use in GB and IE Installation Instructions Heatranger 480D A At t t th he e H He ea ar...

Страница 3: ...Glass Yarn Mineral Wool Insulation Pads Ceramic Fibre May be harmful if inhaled May be irritating to skin eyes nose and throat When handling avoid contact with skin or eyes Use disposable gloves face...

Страница 4: ...nce L H side panel Oil Inlet R1 4 1 4 BSP Taper Ext Electrical Supply 230V 50Hz 3 amp Fused Flue Outlet 150mm CO2 BOILER 11 5 COOKER 11 0 Max Water Temp 82 C Water Capacity of 25 5 litres Boiler Weigh...

Страница 5: ...5 29 3 23 5 OIL PRESSURE Bar psi OIL BURNING RATE cc m HEAT INPUT kW BOILER OUTPUT kW 480K COOKER BURNER BOILER BURNER BURNER NOZZLE US g h 0 40 80 SF 9 0 130 17 6 0 8 MAX 9 0 130 29 3 23 5 OIL PRESS...

Страница 6: ...ngland Wales Part J Heat producing appliances Building Standards Scotland Technical Standard Part F Heat producing appliances and storage of liquid and gaseous fuel Building Regulations Northern Irela...

Страница 7: ...torage tank to the appliance must be fitted with a remote acting fire valve operating at 150 F fitted with an appropriate length of capillary to enable the valve body to be located externally at the p...

Страница 8: ...Site requirements 7 DESN 510519 FIG 1...

Страница 9: ...iance must not be less than the equivalent area of 150mm diameter flue pipe and be at least 4 5m high The flue pipe must not be less than 150mm internal diameter Flue pipes and fittings between the ap...

Страница 10: ...uld be positioned in the vertical plane to reduce the risk of blockage Ducts should be sized so as to reduce resistance to air flow 4 The ventilation requirement for kitchens in Part F of the Building...

Страница 11: ...bject to a maximum head of 18 25m The heating system must be designed and adjusted if necessary to give a temperature differential across the boiler at full output of 10 14 C When horizontal runs are...

Страница 12: ...tion with the hot water channel gives priority to either the domestic hot water or the supply of hot water for central heating DHW if external controls are fitted It is recommended that independent te...

Страница 13: ...The installation should be protected by a 30mA Residual Current Circuit Breaker RCCB The minimum requirement for the power cable is that it should be a 3 core PVC sheathed flexible cord 85 C min at l...

Страница 14: ...13 Site requirements FIG 4...

Страница 15: ...ust be an air gap of 25mm between the wall and the rear of the cooker Fit the rear distance brackets as shown in Fig 5 Whenever possible it is recommended that the skirting board is removed for the wi...

Страница 16: ...inate the flue system in accordance with the regulations in force 4 Lift up the insulating covers and remove the hotplate using lifting hooks provided See Fig 7 5 Remove the insulation pad B 6 Remove...

Страница 17: ...e valve through the grommet in the left hand side panel and locate in the clips provided 2 Connect the flexible hose to the outlet pipe from the oil filter 3 Before connecting the flexible oil pipe to...

Страница 18: ...NDER STAT ZONE VALVE S ETC IF FITTED PUMP SUPPLY THE CIRCULATING PUMP MUST BE CONNECTED DIRECTLY TO THIS SUPPLY PUMP SUPPLY THE CIRCULATING PUMP MUST BE CONNECTED DIRECTLY TO THIS SUPPLY 3 AMP PERMANE...

Страница 19: ...n open allowing the burner to fire Until all the air from the oil pump is flushed out there may be some flame instability resulting in the burner locking out This will be shown by the burner stopping...

Страница 20: ...w and insert the sensing end of a portable indicator to check the CO2 Carbon Dioxide level Adjust the boiler burner air intake until a reading of 11 5 CO2 is recorded on the indicator Check Smoke Remo...

Страница 21: ...ing the water flow rate through individual heat emitters to ensure a satisfactory water temperature at each emitter 5 When the water system reaches working temperature check that the boiler thermostat...

Страница 22: ...ed from a service pipe under mains pressure provided that this pressure is acceptable to the local water authority See Fig 20 SEALED SYSTEM REQUIREMENTS Air or Nitrogen charge pressure bar Pre Pressur...

Страница 23: ...Sealed Systems 22...

Страница 24: ...23...

Страница 25: ...24...

Отзывы: