32
D)
Momentarily depress
to advance to HIGH OFFSET FOR PWM SYSTEM.
18)
HIGH OFFSET FOR PWM SYSTEM
A)
Place the flow control switch to MAN and boom switch to ON.
B)
Hold INC/DEC switch to INC until desired maximum RPM of system is reached.
C)
Hold INC/DEC switch to DEC until RPM of system starts to slow down.
D)
Decrease the number in oFHi by 10.
E)
Repeat steps b, c, and d until desired maximum RPM cannot be reached when
holding INC/DEC switch to INC.
F)
Increase the number in oFHi by 10.
G)
Hold INC/DEC switch to INC.
H)
Repeat steps f and g until maximum RPM is reached.
I)
Increase the number in oFHi by 10. High Offset is now set.
J)
Momentarily depress
to advance to LOW OFFSET FOR PWM SYSTEM.
19)
LOW OFFSET FOR PWM SYSTEM
A)
Place the flow control switch to MAN and boom switch to ON.
B)
Hold INC/DEC switch to INC until system starts to run.
C)
Hold INC/DEC switch to DEC until system stops running.
D)
Increase the number in oFLo by 10.
E)
Repeat steps b, c, and d until system will not stop running when holding
INC/DEC switch to DEC.
F)
Decrease the number in oFLo by 10.
G)
Hold INC/DEC switch to DEC.
H)
Repeat steps f and g until system stops running.
I)
Decrease the number in oFLo by 10. Low Offset is now set.
J)
Momentarily depress
to advance to PWM FREQUENCY.
20)
PWM FREQUENCY
A)
RATE display will show "FrEq". DATA display will show "122".
B)
Enter the desired frequency as recommended by the PWM Valve manufacturer.
C)
Momentarily depress
to advance to DUAL SENSOR ALARM.
21)
DUAL SENSOR ALARM
A)
RATE display will show "dSA". DATA display will show "50".
B)
Enter the desired percent for the alarm.
C)
Momentarily depress
to advance to CONSOLE DATA PRINTOUT.
NOTE:
Some options within the DATA MENU LISTINGS may be unavailable if certain features
are on or active. The options affected are:
CONSOLE DATA PRINTOUT:
Console Data Printout will not be available when DATA
LOGGER is ON or when GPS functions are ACTIVE.
GPS OPTIONS:
GPS Options will not be available when DATA LOGGER is ON.
DATA LOGGER:
DATA LOGGER will not be available when GPS functions are
active.