- 19 -
V02 en, SCC_WE
Manual modes SCC_WE / Boiling point recognition
Steam mode in relation to boiling point recognition
During self test (after initial installation) the unit will determine the installation altitude by water boiling
point recognition.
As the boiling temperature declines with increasing altitude above sea level, the water boiling point
determines the installation altitude.
During self test the steam production will be active until the quenching sensor B2 reaches 70°C
(158°F). At this time the pcb will memorise the temperature measured by the interior cabinet sensor B1
as the boiling point temperature at the actual point of installation.
To run a manual cooking mode the following steps must be taken:
1. Cooking mode is selected.
2. Time or core temperature is selected.
3. Cabinet door is closed (door contact).
4. Fan motor is running (speed signal via bus).
5. In wet modes (Steam, Combination) the steam generator must be filled with water (level electrode)
6. In wet modes (Steam, Combination) the steam generator will be preheated
(thermocouple steam generator)
Mode
Temperature
range
Responsible sensor
30° (87°) up to
boiling point
Cabinet sensor B1 controls steam heating
- Humidity setting not possible
at boiling point Cabinet sensor B1 controls steam heating
- Humidity setting not possible
above boiling
point up to
130°(266°)
Humidity control (P1, M1 rpm and B4) controls steam heating,
Cabinet sensor B1 controls Hot air heating at 50%, (only
possible when humidity is above 70%)
- Humidity setting not possible
30° (87°) up to
boiling point
Cabinet sensor B1 controls Hot air heating up to set temp.;
Cabinet sensor B1 controls steam heating
above boiling
point up to
300°(572°)
Cabinet sensor B1 controls Hot air heating up to set temp.;
Humidity control (P1, M1 rpm and B4) controls steam heating,
30 - 300°C
(86 - 572°F)
Alternating supply of steam and hot air depending on the reached
temperature and humidity.
- Humidity setting is possible
30 - 300°C
(86 - 572°F)
Cabinet sensor B1 controls Hot air heating
- Humidity setting is possible (humidity from food only)
Quenching controlled by B2 at 80°C (176°F) Wet, 90°C (194°F) in Hot Air