6 | Electrical connection
44 / 72
80.06.231_iVarioProL-iVarioProXL_IM_en-GB
3 AC 400 V
Power kW
Amp draw A
Fuse A
Conductor cross-sec-
tion mm²
iVario Pro L
27
39
40
6
iVario Pro XL
41
59
63
10
3 AC 415 V
Power kW
Amp draw A
Fuse A
Conductor cross-sec-
tion mm²
iVario Pro L
29
41
50
10
iVario Pro XL
44
61
63
10
3 AC 440 V
Power kW
Amp draw A
Fuse A
Conductor cross-sec-
tion mm²
iVario Pro L
25
33
40
6
iVario Pro XL
38
50
50
10
3 AC 480 V
Power kW
Amp draw A
Fuse A
Conductor cross-sec-
tion mm²
iVario Pro L
29
35
35
6
iVario Pro XL
44
53
60
10
6.8
Socket in the unit
Version without residual current circuit breaker:
The socket in the unit is equipped with a 10 A fuse. The maximum available
power is 2,3 kW.
Version with residual current circuit breaker:
The socket in the unit is fitted with an integrated RCD, which disconnects the
socket if there is any current leakage.
1. Check the socket in the unit before first use.
2. Regularly check the residual current circuit breaker according to the coun-
try-specific regulations.