 Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020

Initiating a System Test

The System Test is started from the Base Station Settings Menu:

1.  Select 

WES MAIN  MENU

System Logs

Settings

The access code is required to access the Settings Menu.  The default 

PIN number is 1234.

  

From the Settings Menu, select System Test to 

start test mode.

The Base Station will display a confirmation message that the test has 

started.  Walk the site to check all units in the network.

System test started

Walk the site to

check all units OK

During System Test mode, the WES

3

 network isolates all devices in the 

network, allowing full physical testing of each unit, without activating 

the site-wide alarm.  Call points can be triggered manually, and 

Detectors can be tested using standard test equipment such as smoke 

spray or a heat probe.

Cancelling a System Test

Once the System Test is complete, return to the Base Station and 

press the    button to complete the test.  It is important to be aware 

that, whilst in System Test mode, the WES

3

 network is inactive and a 

site wide alarm cannot be triggered from any unit.  The test must be 

exited from the Base Station in order to reactivate the network.

Note : Following initial installation, wait for a minimum of 60 minutes 

before starting the first system test.  During this time, the WES

3

 units 

will self-calibrate to adjust for background radio noise which may 

impact the accuracy of the system test.

The test result is indicated as follows:

Pass 

Green LED solid illumination

Radio OK, other fault 

detected 

Red LED flashes followed by Amber LED 

group flashes to indicate fault (see ‘Amber 

LED Indication’).

No Radio Signal 

Amber LED group flashes to indicate fault 

(see ‘Amber LED indication’).

System Integrity Test (Polling)

WES

includes a System Integrity Test that can report on changes to 

the network configuration, such as when additional or unexpected units 

are detected on the network, or when units have been removed.

The Integrity Test is conducted automatically twice daily, and can also 

be activated on-demand from the WES

Base Station.  To activate the 

Integrity Test, go to the Settings Menu of the Base Station.  The access 

code is required to access the Settings Menu.  The default PIN number 

is 1234.

  

From the Settings Menu, select System Poll to initiate the 

integrity test.

While the Integrity Test is being performed, the message “System Poll ; 

Listening...” will be displayed on the screen.

System poll

Listening...

Any additional units that have been found on the network since the 

last system poll will be displayed as a ‘NEW’ notification on the Base 

Station.  Any units that have been removed from the network since the 

last system poll will be displayed as a ‘GON’ notification on the Base 

Station.

In addition to the automatic system integrity test and the on-demand 

polling feature, WES

3  

provides immediate real-time notification when 

a unit is removed from the network, displayed on the Base Station as 

a ‘REM’ notification.  Note that system polling is limited to the first 128 

WES

 units added to the network.  Beyond this number, further units 

can be added but will be excluded from the integrity test.

System Tests

SETTINGS MENU

Unit Numbering

System Test

System Poll 

SYSTEM WARNINGS

04/11 14:39  101 NEW

04/11 14:39  098 GON

04/11 14:39  014 GON

Содержание WES3

Страница 1: ...Page 1 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 WES3 User Guide and Operation Manual Visit the Members Area on www wesfire com for How To videos...

Страница 2: ...Initial CONNECT Setup Language Selection Inspection Delay Pre Alarm Mode Creating a network Allocate unit numbers Adding units to an existing group Position units on site Securely fix the units in pla...

Страница 3: ...unications User Phone Details Test Phone Number GSM Status SIM Card Information Network Scan Change Site Name Power Off WES3 Base Station Basic System Setup Initial Base Station Setup Language Selecti...

Страница 4: ...st Polling Moving a Unit on Site Removing a Unit from the Site Base Station Operation Menu Overview Alarm System Warnings WES Warning Code Guide Base Station Controls Home Screen System Logs Settings...

Страница 5: ...nical Data Heat Detector Technical Data Smoke Detector Technical Data Interface Technical Data Link Technical Data Heat Detector Maintenance Routine Inspection Operational Test Function Test Cleaning...

Страница 6: ...nd Strobe LED Indicators Call Point Heat Dectector LED Indicators LCD Display Navigation Pad Smoke Detector Cable Gland CONNECT Heat Detector Units Link Base Station Smoke Detector Units Interface Ant...

Страница 7: ...from an external trigger and set off the alarm on the WES3 system System Overview All WES3 units have three indicator LEDs plus two push buttons labelled A and B Some units have additional buttons an...

Страница 8: ...ansported in boxes of 8 Refer to Product Datasheets for full details of unit weights Unopened boxes should be stacked no more than 10 high on a solid stable surface Individual unboxed units should not...

Страница 9: ...Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Fire Pont Technical Data WES3 CONNECT Basic System Setup The following pages 10 26 detail the setup of a network using a WES3 C...

Страница 10: ...od between triggering a call point and the site wide alarm being raised This can allow time for the incident to be validated on site and a decision to be made to either i confirm alarm is genuine rais...

Страница 11: ...ck the settings displayed on screen are the desired settings and if not repeat the Initial CONNECT Setup process before proceeding Basic System Operation 2 Creating a network A network can be made up...

Страница 12: ...site are adhered to such as BS 5839 1 in the UK Wherever possible avoid positioning the unit directly adjacent to metal frames metal surfaces electric cables and similar equipment that may interfere w...

Страница 13: ...the accuracy of the system test Raising the Alarm Manual activation To raise the alarm press any call point in the system The call point will latch into the pressed position and a mechanical yellow a...

Страница 14: ...edical alert The default PIN number is 1234 During the re arm period the alarm cannot be reactivated It is therefore vital to confirm that there is no fire hazard before silencing the alarm Resetting...

Страница 15: ...d upon as part of the fire alarm and detection system until the fault has been corrected Use the chart below to determine the nature of the issue Group Flash 1 Low Battery Group Flash 2 Low signal Gro...

Страница 16: ...atically twice daily and can also be activated on demand from the WES3 CONNECT unit To activate the Integrity Test go to the Test Menu and slect System Poll to initiate the integrity test While the In...

Страница 17: ...ion buttons will activate the display If there are no current warnings or fire alarms across the system the CONNECT unit will display the home screen which shows the site name and the date and time Pr...

Страница 18: ...olved Alarm When an alarm has been raised by a Call Point or Detector the CONNECT unit will flash the LCD display beep and display ALARM ALARM ALARM together with which units raised the alarm The newe...

Страница 19: ...f its battery is flat No INT Internal Tamper Unit NNN has been opened No LAT Latched Call point button on unit NNN is still depressed Yes REM Removed Unit NNN has been deactivated and removed No SIG L...

Страница 20: ...order with the newest at the top of the list Each log entry has the date and time the event was logged followed by the unit number and type and then a or symbol to indicate the raising or clearing of...

Страница 21: ...ns on both the CONNECT and the unit you are numbering The amber LEDs on both units will illuminate and then the green LEDs will flash to confirm successful renumbering Stop pressing the A button when...

Страница 22: ...ght This feature deactivates the rear tamper so the unit is Mobile The CONNECT unit can be made mobile by pressing the relevant Soft Key on the Mobile base option A highlighted button indicates that t...

Страница 23: ...d deselected by pressing the corresponding number key or the arrow Soft Key nearest to the symbol Settings Test Phone Number Pressing the arrow Soft Key nearest the Press to Start icon will initiate a...

Страница 24: ...desired network is confirmed by pressing R Change Site Name The site name appears on the Home Screen and is included in every text message so that you can quickly identify the source of the alarm or w...

Страница 25: ...stallation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Fire Pont Technical Data WES3 Base Station Basic System Setup The following pages 28 45 detail the setup of a network using a WES...

Страница 26: ...ximum 10 minutes A confirmation screen will be displayed to validate the setting and prevent accidental activation Basic System Setup Base Station version if applicable to your system Alarm delay sele...

Страница 27: ...nd adding to a WES3 network Access the Settings Menu on the Base Station home screen The Settings menu can be accessed from the Main Menu by selecting Settings with the directional pad then pressing E...

Страница 28: ...mper is fully depressed 7 Test the system After installation of the units it is essential to perform a system alarm test to confirm proper operation of the system It is also best practice to conduct a...

Страница 29: ...reset to cancel the alarm Please wait for 5 seconds between pressing and resetting a call point After the alarm has cleared the system has a short 2 minute re arm period during which the sirens will s...

Страница 30: ...nit latched potentially input latched on Interface unit only Red LED Indication If a detector has raised the alarm its red LED indicator will flash during a fire alarm It is recommended that the fire...

Страница 31: ...ult detected Red LED flashes followed by Amber LED group flashes to indicate fault see Amber LED Indication No Radio Signal Amber LED group flashes to indicate fault see Amber LED indication System In...

Страница 32: ...oving it to another site it must first be deactivated in order to prevent accidental triggering preserve battery unit life clear site information which would prevent it forming or joining another site...

Страница 33: ...e are no current warnings or fire alarms across the system the base station will display the home screen which shows the site name and the date and time Pressing enter goes to the main menu to allow s...

Страница 34: ...se Station will flash the LCD display beep and display ALARM ALARM ALARM together with which units raised the alarm The newest event will be at the top of the list Units are identified by unit number...

Страница 35: ...has been removed from wall ceiling Yes 4 FLT Flat Battery Unit NNN has turned off its battery is flat No 5 INT Internal Tamper Unit NNN has been opened No 2 LAT Latched Call point button on unit NNN i...

Страница 36: ...top of the list Each log entry starts with the date and time the event was logged followed by the unit number and type and then a or symbol to indicate the raising or clearing of an event If there is...

Страница 37: ...WES3 unit needs to be numbered when first paired to the WES network This unit number can be changed using the Unit Numbering feature and any number between 001 and 999 may be used avoid duplicating n...

Страница 38: ...ring Screen A unit whose amber LED fails to illuminate will not pair This may be due to an internal tamper Date and Time The date and time can be updated in the Date and Time screen using the navigati...

Страница 39: ...isable site location The site name is edited using the navigation pad and confirmed by pressing enter Communications User Phone Details The user phone details allows up to six users names and telephon...

Страница 40: ...ctor head removed 4 External tamper Unit NNN has been removed from the wall ceiling 5 Low battery Unit NNN has low battery 6 Low signal Unit NNN has a low radio signal 7 System test Unit NNN has initi...

Страница 41: ...ge type site name time and date as shown below WES3 Base Station Text Message Sent from DEFAULT SITE at 14 12 57 on 29 July 2018 29 Jul Note that the SMS messaging feature of WES3 is intended for noti...

Страница 42: ...Page 42 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Call Point Technical Data Call Point strobe and sounder Call Point sounder...

Страница 43: ...UK 1200Hz falling to 500Hz over 1 sec silence 10ms Germany 554Hz for 100ms and 440Hz for 400ms France Minimum A weighted sound at 1 metre Position Horizontal Plane dB A Vertical Plane dB A 15 83 7 85...

Страница 44: ...500Hz over 1 sec silence 10ms Germany 554Hz for 100ms and 440Hz for 400ms France Minimum A weighted sound at 1 metre Position Horizontal Plane dB A Vertical Plane dB A 15 83 7 85 3 45 89 4 91 6 75 96...

Страница 45: ...Page 45 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Fire Pont Technical Data CONNECT Technical Data CONNECT control unit...

Страница 46: ...e Channel spacing Single channel Compatible with Other WES3 units Protocol Proprietary The Radio Frequency RF range complies with the Phase II EGSM 900 DCS 1800 recommendation and LTE Cat 1 3GPP Relea...

Страница 47: ...Page 47 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Fire Pont Technical Data Base Station Technical Data Base Station...

Страница 48: ...average Current consumption 120 A average Battery type Alkaline primary cells 23Ah RF Parameters Operating frequency 868 2MHz Transmit power 25mW max Duty cycle 1 Encryption None Channel spacing Sing...

Страница 49: ...Page 49 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Heat Detector Technical Data Heat Detector...

Страница 50: ...ty Relative humidity 95 non condensing 25 C to 55 C Heat detector class A2 Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 2 7mW average Current consumption 520 A averag...

Страница 51: ...y Relative humidity 95 non condensing 25 C to 55 C Heat detector class A2 Supply Parameters Operating voltage range 4 0 6 4V from internal battery Power 1 3mW average Current consumption 240 A average...

Страница 52: ...Page 52 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Smoke Detector Technical Data Smoke Detector...

Страница 53: ...5 C to 70 C Humidity Relative humidity 95 non condensing 25 C to 55 C Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 2 7mW average Current consumption 520 A average Bat...

Страница 54: ...ture 25 C to 70 C Humidity Relative humidity 95 non condensing 25 C to 55 C Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 1 3mW average Current consumption 240 A avera...

Страница 55: ...Page 55 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Interface Interface...

Страница 56: ...systems etc may require additional measures Cable disconnection or damage could result in the alarm not activating when required without any fault or warning indication All cable lengths must be less...

Страница 57: ...5 C Humidity Relative Humidity 95 non condensing 25 C to 55 C Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 770 W average Current consumption 150 W average Battery typ...

Страница 58: ...Page 58 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Link Technical Data Link...

Страница 59: ...C to 70 C Humidity Relative humidity 95 non condensing 25 C to 55 C Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 620 W average Current consumption 120 A average Batte...

Страница 60: ...e 25 C to 70 C Humidity Relative humidity 95 non condensing 25 C to 55 C Supply Parameters Operating voltage range 4 4 6 4V from internal battery Power 600 W average Current consumption 110 W average...

Страница 61: ...Note Hot air blowers sold for paint stripping soldering pipes etc generate sufficient heat to damage the detector and should not be used for testing heat detectors iii After the detector has given the...

Страница 62: ...rm the detector s correct operation in response to a heat condition i Testing the detectors will trigger the site wide alarm To avoid unnecessary evacuation site personnel should be informed when test...

Страница 63: ...xclusive to the website you must be logged in to view them Ramtech Customer Support Technical advice is available over the phone by contacting Ramtech Customer Support and site visits can be arranged...

Страница 64: ...Page 64 WES3 Installation and Operations Manual V2 0 Ramtech Electronics Limited 2020 Tel 44 0 115 822 3424 Email wes ramtech co uk Web www wesfire com V2 0 10 2019...

Отзывы: