Page 19
WES
3
Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
CONNECT Pad Controls
The
R
key is used to enter the Main Menu from the Main Screen. It is
also used to confirm a selection/data entry.
The
Q
key is used to exit from menus. It is also used to cancel a
selection/data entry.
The numeric keys are used to enter data.
WES Warning Code Guide
Warning Code
Warning
Description
Self-Clearing
MED
Medical Assist
Medical assistance required at Unit NNN
No
BAT
Low Battery
Unit NNN has a low battery
No
DET
Detector Tamper
Unit NNN has had detector head removed
Yes
EXT
External Tamper
Unit NNN has been removed from wall/ceiling
Yes
FLT
Flat Battery
Unit NNN has turned off, its battery is flat
No
INT
Internal Tamper
Unit NNN has been opened
No
LAT
Latched
Call point button on unit NNN is still depressed
Yes
REM
Removed
Unit NNN has been deactivated and removed
No
SIG
Low Signal
Unit NNN has a low radio signal
Yes
TST
System test
Unit NNN initiated a System test
Yes
NEW
Unexpected unit
Unit NNN added since last system poll
No
GON
Unit missing
Unit NNN removed since last system poll
No
Soft Keys
The function of each key is displayed on screen and varies depending
on the screen displayed.
Home Screen
Pressing
R
on the home screen opens the Main Menu, giving access
to the System Log Menu, Unit Numbering Screen, Test Menu, Power
Off screen and the Settings Menu. The settings are only available to
authorised users with an access code.
If the CONNECT unit has not yet been paired, it will display ‘Unpaired’
instead of the site name.
Advanced
CONNECT Operation
Screen