CONDITION

NO LIGHTS ARE 'ON'.

GATE MOVES A COUPLE
OF FEET AND THEN
REVERSES.

"EXIT" L.E.D. IS ALWAYS
'ON'.

"REV LOOP" L.E.D.
ALWAYS 'ON'.

"RADIO" L.E.D. ALWAYS
'ON'.

GATE DOESN'T OPEN.

GATE DOESN'T CLOSE.

GATE DOESN'T CLOSE
AUTOMATICALLY.

GATE AUTOMATICALLY
OPENS, BUT DOESN'T
AUTOMATICALLY CLOSE.

RADIO/RECEIVER HAS NO
RANGE.

POSSIBLE CAUSES

1. Circuit breaker popped. 
2. 1/2 amp. fuse blown.
3. Power supply damaged on

Control Board.

1. E.R.D. too sensitive.

1. Faulty accessory connected

to the "Exit".

1. Faulty accessory connected

to the "Rev Loop".

1. Stuck button on Transmitter
2. Faulty Receiver.

1. Radio L.E.D. 'On'.
2. 10 amp. fuse blown.
3. Opening accessory not func-

tioning.

1. No lights are 'On'.
2. Exit, Rev Loop, Radio L.E.D. 'On'.
3. 10 amp. fuse blown.
4. Thermal/overload button

popped on motor.

1. Dip switches "A" 1-3 are all

'Off'.

2. Dip switch not on all the way.

1. Motor direction wrong.

1. Signal blocked.
2. Area not suitable for type of

Receiver.

SOLUTION

1. Reset circuit breaker.
2. Replace 1/2 amp. fuse.
3. Return Control Board for repair.

1. A) for 1/2 hp motors: turn dip switch 

"A" 4 'On'.

B) for 3/4 hp motors: turn dip switch 
"B" 8 'On'.

1. Disconnect all accessories, including

plug-ins, using the "Exit" input.

If problem persist, contact Ramset.

1. Disconnect all accessories, including

plug-ins, using the "Rev Loop" input.

If problem persist, contact Ramset.

1. Check all transmitters.

2. Remove receiver.

If problem persist, contact Ramset.

1. See above symptoms/solutions.

2. Check/replace 10 amp. fuse.

3. Check/replace opening accessory.

1. See above symptoms/solutions.

2. See above symptoms/solutions.

3. Check/replace 10 amp. fuse.

4. Reset thermal/overload button on the

back of the motor.

1. Set dip switches "A" 1-3 for auto

close.

2. Turn off dip switches "A" 1-3, then

turn the appropriate switches back
'On'.

1. Turn on dip switch "C" 7 (left/right).

1. Make sure antenna is in proper posi-

tion & not shorted to chassis.

2. May need to change to long range

receiver.

TROUBLESHOOTING TABLE

R_Ramset_Ram3000.qxd  8/19/05  4:58 PM  Page 23

Содержание RAM 3000 UL

Страница 1: ...FOR CLASS I II III IV VEHICULAR GATE OPERATORS R_Ramset_Ram3000 qxd 8 19 05 4 56 PM Page 1...

Страница 2: ...www ramsetinc com R_Ramset_Ram3000 qxd 8 19 05 4 56 PM Page 2...

Страница 3: ...death 1 READ AND FOLLOW ALL INSTRUCTIONS 2 Never let children operate or play with gate controls Keep the remote control away from children 3 Always keep people and objects away from the gate NO ONE S...

Страница 4: ...Y DEVICE SUCH AS A PHOTOELECTRIC EYE OR LOOP DETECTOR CHECK THE E R D SENSITIVITY MAKE SURE THAT ALL AREAS AROUND THE GATE ARE SAFE AND SECURE SUCH AS THE FRONT REAR AND TRAVEL AREA COMMUNICATE WITH T...

Страница 5: ...ature to prevent unauthorized use f All warning signs and placards must be installed where visible in the area of the gate g For Vehicular Gate Operators utilizing a non contact sensor in accordance w...

Страница 6: ...s III A vehicular gate operator or system intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public Re...

Страница 7: ...tion 1 4 H R Metal 1 4 H R Metal 1 4 H R Metal Continuous Duty 1 2 Hp 120 Vots AC 3 4 Hp 120 Vots AC 1 Hp 220 Vots AC Motor 4 5 amp 1625 rpm 8 5 amp 1625 rpm 4 5 amp 1625 rpm Power Failure By hand lev...

Страница 8: ...be adjusted depending on local soil conditions 1 Construct form for mounting pad according to dimensions shown in Figure 1 and 2 2 Locate mounting pad according to dimensions given in illustration 3...

Страница 9: ...LENGTH Figure 5 Figure 3 Note 15 amp wires connected to independent breaker HOOKUP ELECTRICAL POWER Figure 4 Gate travel is adjusted by loosening the limit Cams and adjusting them until proper gate tr...

Страница 10: ...com RAMSET RAM 3000 UL 3100 UL 3200 UL SPACE REQUIRED FOR A STANDARD GATE IN THE OPEN POSITION Figure 7 STANDARD INSTALLATION FOR GATES FROM 16 TO 22 IN LENGTH Figure 6 R_Ramset_Ram3000 qxd 8 19 05 4...

Страница 11: ...9 www ramsetinc com RAMSET RAM 3000 UL 3100 UL 3200 UL MINIMUM SPACE REQUIRED FOR COMPACT INSTALLATION Figure 8 Figure 9 20 minimum space required between open gate and wall for this compact installa...

Страница 12: ...Loops on the ground floor prevents gate from closing when vehicle is in loop area Exit Loops on the ground floor opens gate when vehicle crosses loop area Photoelectric Safety Sensor Photo Eye preven...

Страница 13: ...gate Control Board Three pushbuttons are located under the dip switches for operation of the gate see Figure 11 The opening stop and closing buttons can be utilized to set limit switches and verify pr...

Страница 14: ...N Relay maintains a closed contact Dip Switch B 3 CONSTANT WARN Constant warning when gate is in motion Sw Function OFF No effect ON Triggers the prewarn relay to maintain a closed contact while gate...

Страница 15: ...Function OFF Master mode single gate operation All peripheral devices are to be connected to the master operator ON Slave mode used to synchronize operation between two gates Commands are received fro...

Страница 16: ...14 www ramsetinc com RAMSET RAM 3000 UL 3100 UL 3200 UL TERMINAL STRIP CONNECTION Figure 14 R_Ramset_Ram3000 qxd 8 19 05 4 57 PM Page 16...

Страница 17: ...detector is cleared Once the detector is cleared the operator will resume normal operation If triggered twice before reaching a limit switch the alarm will sound for 6 minutes and the control board w...

Страница 18: ...rol Board is powered by a separate mounted 24 VAC transformer This allows no neces sary board modifications between 110 VAC and 220 VAC single phase applications Some of the functions of the Control B...

Страница 19: ...e The open and close are normally open connections and the stop is a nor mally closed connection remove jumper wire when connecting 3 button station Common and stop are also used with a photo eye used...

Страница 20: ...42 27 24 65 71 64 30 39 34 37 41 63 40 45 63 35 63 59 29 58 47 50 49 27 25 31 26 26 27 24 66 33 60 53 33 54 38 57 62 61 1 9 3 6 7 8 5 4 2 43 67 44 57 13 13 38 30 24 52 51 28 27 10 57 18 70 22 48 25 1...

Страница 21: ...lley 1 1 1 19 50 071 2 1 2 Cast Iron Pulley 1 1 1 20 50 076 4L V Belt 170 1 1 1 21 50 085 35 Limit Switch Chain 1 1 1 22 50 086 40 Driver Chain 26 Links 1 1 1 23 50 091 6 x 1 Machine Screw 2 2 2 24 50...

Страница 22: ...3 16 x 3 4 Key Way 4 4 4 58 50 275 1 1 2 UHMW Spacer 1 1 1 59 50 295 8 Self Tap Sheet Metal Screw 2 2 2 60 50 299 Radio Receiver Terminal 1 1 1 61 50 304 120 240 Intelligate Transformer 1 1 1 62 50 31...

Страница 23: ...1 Signal blocked 2 Area not suitable for type of Receiver SOLUTION 1 Reset circuit breaker 2 Replace 1 2 amp fuse 3 Return Control Board for repair 1 A for 1 2 hp motors turn dip switch A 4 On B for 3...

Страница 24: ...estrians should use a separate entrance 3 Always keep people children and objects away from the gate while the gate is in operation No one should cross the area of a moving gate 4 All opening devices...

Страница 25: ...eration No one should cross the area of a moving gate Use the emergency release only when the gate is not moving Make sure when using the foot release or hand crank the circuit breaker for the operato...

Страница 26: ...ry System Key Switch Box Ramset Radio Receiver Ramset Remote Control Transmitter ILD 24 Ramset Plug in Loop Detectors Uphill Hinges Uphill Arms To be used under uneven conditions 20 05 50 40 Mounting...

Страница 27: ...www ramsetinc com R_Ramset_Ram3000 qxd 8 19 05 4 58 PM Page 27...

Страница 28: ...R_Ramset_Ram3000 qxd 8 19 05 4 58 PM Page 28...

Отзывы: