Copyright 2020, Al-Rakeb Oil, Electricity & Construction Services Company | Kuwait
52
Issue
Diagnose
Solution
Dispenser has no
power thus monitor is
not lit.
Check electric connection and power
cables connection.
If damaged, replace. If it is not
connected, connect.
Check power card inside the dispenser.
If damaged, replace.
Check the circuit breaker of the dispenser
in the electrical box.
If it is off turn it on. If it is
damaged, replace
Make sure that the power being received
to the dispenser is 230 VAC.
Make sure that the power cable
is not damaged. If damaged
replace.
Leakage took place
and the product inside
the tank decreased but
the leak alarm is not
working.
Check power source to the leak alarm
console.
If not connected, connect.
Check if the leak sensor is working.
if not working, replace
Check the electrical connection from the
sensor to the alarm console.
Check the conductivity of the
wires, if not conducting properly
replace wire.
Check the unit console itself
If it is not working or
malfunctioning. Replace.
Содержание Mobile Filling Station
Страница 12: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 12 Figure 8 Control room entrance...
Страница 13: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 13 Figure 9 Shows the control room...
Страница 43: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 43 4 5 6 7...
Страница 63: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 63...
Страница 64: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 64...
Страница 66: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 66...
Страница 68: ...Copyright 2020 Al Rakeb Oil Electricity Construction Services Company Kuwait 68...