Rain Master Irrigation Systems
Weather Station Manual
Page 33
5.2.4 Symptom: No Wind Reading
No
1
Check bearings and
cup assembly
mounting.
Ref. Installation
instructions Check wiring
and verify polarity. Figure
6, page 10.
Disconnect the two wires from the
Sensor Terminal at terminals Input 4
(+) and Input 4 (-) and re-measure
voltage. If voltage reads 0, contact
factory. If voltage reads +8 VDC,
problem lies in wiring or rain gauge.
If voltage reads +8 VDC, reconnect the two
wires to the Sensor Terminal board Inputs
4(+) and 4(-). At the tower terminal block,
unplug the rain gauge connector. Re-
measure voltage at terminals Input 4(+) and
4(-). If voltage reads +8 VDC, problem lies in
rain gauge. If voltage reads 0, check for
shorts in cable and terminal block
connections.
Reconnect the two wires
to the Sensor Terminal
board Inputs 4(+) and 4(-).
Start
Does the wind
cup assembly
spin freely?
Is the
wind sensor from
Weather Station
wired correctly to the
DX2 controller?
Yes
No
Can
+8 Volts DC
be measured at terminal
Inputs 4+ and 4- of the
Sensor Terminal
board?
Yes
No
Yes
1
2
3
4
Содержание ET Tracker
Страница 1: ...Weather Station User Manual ET Tracker Rain Sensor Wind Sensor March 2001Document Number 500009 Rev C ...
Страница 2: ......
Страница 3: ...Rain Master Irrigation Systems Weather Station Weather Station ...
Страница 4: ......
Страница 8: ...Rain Master Irrigation Systems Weather Station Manual Page 3 Figure 1 Weather Station Configuration ...
Страница 11: ...Weather Station Manual Rain Master Irrigation Systems Page 6 Figure 2 Weather Station Tower Base ...