Page
56
NOTE !
Remember that you have a
“spare” pair of communication wires in
the Belden #9883 cable. Using this
spare pair substitute it for one of the
other pairs and test again. If it is not
this pair that are “bad” then substitute
the “spare” pair for the other pair and
test again. In this way you should be
able to determine which pair are “bad”
and use the “spare” pair in their place.
FIGURE 26 - TEST OF COMMUNICATION WIRE
A “WS-PRO-PH” PHONE
CONNECT WEATHER STATION
Weather Station will not answer.
•
Check the weather station for
operation on it’s own to be sure it is
functioning properly. This will
verify the proper voltage coming into
the weather station and also if the
datalogger checks out O.K.
•
Connect a telephone to the phone
line at the weather station and call
out, or have someone call in.
Listen for any noise on the line.
Refer to NOTE below.
NOTE !
A phone line going to the
computer or to the weather station itself
MUST BE DATA QUALITY
. You can
talk over a phone line that will NOT
allow data communication.. Listen for
any fuzzy noises and any disturbance at
all. You must be sure the phone line is
“Good”. Time and time again we have
set up stations and the phone line is
NOT good enough for communication.
Make sure the phone company knows
this will be for data communication.
Have Phone Company check line ALL
the way back to the weather station.
•
If the station is still not answering,
get your volt/ohm meter and measure
across the phone line. It should read
approximately 48 Volts DC, with
the Ring as the positive side and the
Tip the negative side.
•
Have someone call in and then
measure the voltage across the phone
line. It should read 90 to 110 Volts
AC. The answer modem switch
circuit requires 40 Volts to activate
and allow the signal to pass to the
datalogger.
•
The Datalogger detects the ring and
raises the modem enable line high
(pin 5), to +5 Volts DC. (Measure
pin 5 to ground).
Содержание WS-PRO
Страница 1: ...WS PRO Weather Station INSTALLATION MAINTENANCE AND TROUBLESHOOTING MANUAL November 2004 GT27145D...
Страница 2: ......
Страница 10: ...Page viii...
Страница 16: ...Page 6 FIGURE 2 MAGNETIC DECLINATION FOR THE CONTIGUOUS UNITED STATE...
Страница 21: ...Page 11 FIGURE 4 CONCRETE BASE DETAIL FIGURE 5 ANCHOR BOLT TEMPLATE DETAIL...
Страница 24: ...Page 14 FIGURE 6 EXTERNAL WIRING DETAIL AT THE PRO SH WEATHER STATION...
Страница 27: ...Page 17 FIGURE 7 EXTERNAL WIRING DETAIL AT THE PRO PH WEATHER STATION...
Страница 33: ...Page 23 FIGURE 10 SOLAR PANEL INSTALLATION DETAIL...
Страница 35: ...Page 25 FIGURE 11 CROSS ARM MOUNTING INSTALLATION OF 034A WIND SENSOR...
Страница 48: ...Page 38 FIGURE 21 INSTALLATION AT CENTRAL COMPUTER FOR DIRECT CONNECTED WEATHER STATION...
Страница 50: ...Page 40 FIGURE 22 INSTALLATION AT CENTRAL COMPUTER FOR TELEPHONE CONNECTED WEATHER STATION...
Страница 73: ...Page 63 FIGURE 28 TYPICAL 3 ROD GROUNDING GRID DETAIL...
Страница 74: ...Page 64 2 Ht o E 2 p i n s 1 t o 3 4 2 Ht o A G p i n s 1 t o 2 FIGURE 29 TESTING OF WIND SENSOR...
Страница 75: ...Page 65 FIGURE 30 TESTING OF SOLAR RADIATION SENSOR...
Страница 76: ...Page 66 FIGURE 31 TESTING OF RAIN GAGE...
Страница 77: ...Page 67 FIGURE 32 TESTING OF TEMPERATURE RELATIVE HUMIDITY SENSOR...
Страница 78: ...Page 68 FIGURE 33 TESTING OF AIR TEMPERATURE PROBE...