Current Section:
Flow Sensor 64
Navigation:
13.1.5 View FloZone Rates
View Flow Rates
Next
View Station Rates
View FloZone Rates
Done
View FloZone Rates
001
0000.0
FloZone
Max GPM
MV(s) 1
FS (s) 1
1
Turn the controller dial to Flow Sensor
2
At the FLOW SENSOR screen, with “
Set Flow Rates
” selected, press
Next
.
3
At the Set Flow Rates screen, press the key to select “
View Flow Rates
”, then press
Next
.
4
At the View Flow Rates screen, press the key to select “
View FloZone Rates
”, then press
Next
.
5
At the FloZone Flow Rates screen, press the and keys to select the desired FloZone
number. The MVs and sensors associated with that flow zone are shown below it. The
maximum flow rate for that FloZone will show to the right.
•
FloZone rates are used by FloManager. The zone rate cannot be set lower than the highest station rate.
13.1.6 Clear Flow Rates
Occasionally it may be desired to clear the previously learned or user entered flow rates and start
over.
Set Flow Rates
Next
Learn Flow
Set Station Rates
Set FloZone Rates
View Flow Rates
Clear Flow Rates
1
At the FLOW SENSOR screen, with “
Set Flow Rates
” selected, press
Next
.
2
At the Set Flow Rates screen, press the key to select “
Clear Flow Rates
”, then press
Next
.
3
The confirmation screen appears; press
Next
to clear flow rates.
4
A confirmation screen shows the process is complete.