background image

11

 

This section relates to the following  models only: 

HN-G-01-1-XXX HN-G-02-1-XXX

6.  FILTRON 1-10 (DC) Manual

The Filtron 1-10 requires minimal to no user programming, the following sections are only related to site specific programming 

requirements.

6.1  Features

•  Modular backflushing controller for automatic filters of 1 to 2 stations.

•  DC controller which also comes with an AC adapter to 12 VDC.

•  The DC model can be powered either by four 1.5V “D” Batteries or 12v DC (via the AC adapter) and it activates up to 2 wired DC latch-

ing solenoids. The voltage for the solenoids switching is boosted by a charge pump.

•  Flushing cycles may be triggered either by time or by the embedded electronic DP sensor reaching the set point, or by a dry contact 

signal from an external DP sensor.

• 

Endless looping problems can be eliminated by detecting repeated consecutive cycles passing beyond a predefined limit.

•  The unit can optionally handle a Pressure-Sustaining / Main valve, and an Alarm output.

•  The unit is equipped with a customized LCD display and key board.

•  The unit counts separately the number of flushing cycles triggered by DP, by time and manually.

6.2  How to program the controller

The controller is equipped with an LCD display and 4 keys as displayed below. When the unit is left untouched for a minute the display 

is switched off and the only life signal is given by a beep sound that can be heard every 20 seconds. The beep can be disabled in the 

programming section. Holding down any of the keys for a few seconds will bring the screen back to life.

The actual DP value. 

Availability only 

when the built in 

electronic DP is used

The DP Set-Point 
Available only when 
the built in electronic 
DP is used

Manual button

The desired flushing 

time per station

Enter button

The desired flushing 
mode. Contains 
either the flushing 
interval or the letters 
"dp" when the 
flushing is triggered 
by dp only

The screen consists of several fields, some of them are editable and some of them are not. For inserting EDIT MODE the ENTER key has to be 

pushed. The EDIT MODE is indicated by blinking of the characters at the currently editable field. Each time the ENTER key is pushed again, 

the next editable field becomes editable and starts blinking. While in EDIT MODE the “+” and “-“ keys can be used for changing the value 

under focus. Pushing the ENTER key again will set the selected value to the current field and move the focus to the next editable field which 

will start blinking. Once entering this process of passing through the editable fields, the user has no way back but by pushing the ENTER key 

repeatedly, he passes through the chain of editable fields until arriving back to the FLUSH TIME field, meeting no more blinking fields.

Содержание HN-G-01 Filter Series

Страница 1: ...rity to operate the equipment WARNING It is extremely dangerous to open the filter or control tubing while under pressure Always depressurize before performing any maintenance or troubleshooting HN G...

Страница 2: ...D THE INSTRUCTIONS BEFORE INSTALLING THE HN G FILTER 1 1 Models This document relates to multiple models of the HN G filter system sections that relate to specific models are indicated as such 1 2 In...

Страница 3: ...filtered out The clean water then exits through the outlet The build up of contaminants on the filter screen creates a differential pressure across the filter Based on a preset Differential Pressure...

Страница 4: ...ten inches above the HN G for safe removal of the filter cover 2 Locate the HN G filter as close to a drain as possible This will maximize the efficiency of the automatic self cleaning 3 An AC to 12V...

Страница 5: ...may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed due to movement during shipping or installation Install an isola...

Страница 6: ...upplied into the HP high pressure and LP low pressure fittings 3 Read the instructions in the following Filtron 1 10 DC Manual 3 4 3 Turning On Water Supply 1 Ensure Drain pipe is securely in the drai...

Страница 7: ...outlet 4 4 2 If Battery Powered 1 Remove the top gray cover push up the sides over the indent 2 Remove the black battery tray and install the 4x D Cell batteries as shown 3 The controller will come t...

Страница 8: ...r by checking the reading on the pressure gauges if installed 4 HN G 01 1 XXX HN G 02 1 XXX models only Remove Low Pressure 5 16 plastic tube from the Inlet to release the pressure and drain the HN G...

Страница 9: ...e cycled in and out a few times to get the grease distributed to the inner O ring seal Two applications of grease and cycling is adequate 5 The Piston may drip water from the lower vent hole This is n...

Страница 10: ...gation controller must be able to program station run times in seconds or a 24 VAC one shot relay capable of delivering a 7 second signal to the filter must be added The backwash time station run time...

Страница 11: ...the unit is left untouched for a minute the display is switched off and the only life signal is given by a beep sound that can be heard every 20 seconds The beep can be disabled in the programming se...

Страница 12: ...to clean Typical differential set point is generally set somewhere between 6 and 9 PSI At this field the user defines the pressure difference between the filter s inlet and outlet that when reached a...

Страница 13: ...nd up 2 The last backflush valve can be cancelled and then its allocated output will be left unused 3 Alarm output Delay Valve and Main Valve when defined will be allocated in this order right after t...

Страница 14: ...ered as a trigger for flushing The following flushing cycles will be triggered by the interval count down only The problem will be considered as solved when the constant indication of the DP sensor wi...

Страница 15: ...ER DP DELAY 30 seconds 5 ENTER LOOPING 10 6 ENTER ALARM No 7 ENTER DELAY VALVE No 8 ENTER VIEW OUTPUT No 9 ENTER Pressure PSI 10 ENTER BEEP Yes No set to No to prevent sign of life beep every 20 secon...

Страница 16: ...sure during Self Clean Solution Make sure water pressure during Self Clean is at least 40 psi Close the isolation valve on Outlet pipe of the HN G Press the M button on the Backwash Controller HN G wi...

Страница 17: ...Very Poor lines Water source should be rated at worst case scenario if water quality varies during the year such as algae blooms during summer A general guide to Water Quality is also shown below Good...

Страница 18: ...llation easier With unions at all recommended spots the filter may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed d...

Страница 19: ...mmodate low flow rate applications where all pressure and flow must be utilized for backwash the controlled outlet valve can also be applied in installation example A and C Pump Isolating valve Isolat...

Страница 20: ...strates a bypass configuration Union fitting Union fitting Pressure gauge Pressure gauge Piston 1 Hydraulic drain valve Union fitting Isolation valve Outlet to irrigation Inlet from pump Drain to drai...

Страница 21: ...TFC 10 06 Clamp MTFC 08 Cover MTFC 07 Hydraulic Motor MTFC 10 51 Collector Assembly MTFC 10 51 1 4 Tubing 6mm Plastic Tube MTFC Hex Nipple 1 MTFC Hex Nipple 1 CI010821W Streight Fitting 1 8 x 8mm MTFV...

Страница 22: ...22 1 Models 2 Models 1 2 1 2 7 1 8 7 1 4 22 13 16 25 5 8 9 15 16 10 9 16 6 7 1 16 G Dimensions 1 PVC SOCKET CONNECTION PESB SCRUBBER VALVE 12 1 8 REF 5 3 4 7 1 16 6 FILTER SERVICE AREA...

Отзывы: