background image

5

2.4.2  Installation requirements

When installing the ¼” plastic tubing into the 

appropriate fittings – push the tubing in hard, it 

should go in about a ¼”. It should be tight into the 

fitting and does not come out when you pull on it. 

Outlet

 

(to irrigation)

Drain 

(to drain)

Inlet

(from pump)

1.25”+

The drain pipe should be a minimum of 1.25” in 

diameter. The length of drain pipe to the drain should 

be as short as possible, with no more than two 

elbows. Any restrictions in the drain pipe will reduce 

the self-cleaning efficiency of the filter.

The HN-G filter cover

 

can be rotated to best fit existing 

plumbing. To rotate the cover, release the clamp, 

rotate the cover, and close the clamp.

Unions are required for ease of maintenance and in 

order to make installation easier. With unions, at all 

recommended spots, the filter may be removed for 

service and any threaded connections can also be 

easily accessed if any of these need to be tightened 

up or resealed due to movement during shipping or 

installation.

Install an isolating valve (not supplied) between:

•  Inlet and the water supply.

•  Outlet union and the irrigation system.

Gauges on the inlet and outlet are highly 

recommended to be able to monitor pressure 

differential visually.

Drain should not discharge under water level, or in 

any way that would provide back pressure, as this will 

impede performance

The drain needs to be unobstructed.

If the drain line is longer than 20 feet then it should be 

up-sized to 1.5” PVC.

All plumbing (inlet, outlet and drain) should be 

supported so stress is not transferred to the filter.

It is highly recommended that 

any PVC fittings (including the 

ones included with the filter) in 

outdoor installations are painted 

to block UV exposure from the sun.  

Enclosed installations with no sun 

exposure do not required the PVC 

to be painted for protection.

Содержание HN-G-01 Filter Series

Страница 1: ...rity to operate the equipment WARNING It is extremely dangerous to open the filter or control tubing while under pressure Always depressurize before performing any maintenance or troubleshooting HN G...

Страница 2: ...D THE INSTRUCTIONS BEFORE INSTALLING THE HN G FILTER 1 1 Models This document relates to multiple models of the HN G filter system sections that relate to specific models are indicated as such 1 2 In...

Страница 3: ...filtered out The clean water then exits through the outlet The build up of contaminants on the filter screen creates a differential pressure across the filter Based on a preset Differential Pressure...

Страница 4: ...ten inches above the HN G for safe removal of the filter cover 2 Locate the HN G filter as close to a drain as possible This will maximize the efficiency of the automatic self cleaning 3 An AC to 12V...

Страница 5: ...may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed due to movement during shipping or installation Install an isola...

Страница 6: ...upplied into the HP high pressure and LP low pressure fittings 3 Read the instructions in the following Filtron 1 10 DC Manual 3 4 3 Turning On Water Supply 1 Ensure Drain pipe is securely in the drai...

Страница 7: ...outlet 4 4 2 If Battery Powered 1 Remove the top gray cover push up the sides over the indent 2 Remove the black battery tray and install the 4x D Cell batteries as shown 3 The controller will come t...

Страница 8: ...r by checking the reading on the pressure gauges if installed 4 HN G 01 1 XXX HN G 02 1 XXX models only Remove Low Pressure 5 16 plastic tube from the Inlet to release the pressure and drain the HN G...

Страница 9: ...e cycled in and out a few times to get the grease distributed to the inner O ring seal Two applications of grease and cycling is adequate 5 The Piston may drip water from the lower vent hole This is n...

Страница 10: ...gation controller must be able to program station run times in seconds or a 24 VAC one shot relay capable of delivering a 7 second signal to the filter must be added The backwash time station run time...

Страница 11: ...the unit is left untouched for a minute the display is switched off and the only life signal is given by a beep sound that can be heard every 20 seconds The beep can be disabled in the programming se...

Страница 12: ...to clean Typical differential set point is generally set somewhere between 6 and 9 PSI At this field the user defines the pressure difference between the filter s inlet and outlet that when reached a...

Страница 13: ...nd up 2 The last backflush valve can be cancelled and then its allocated output will be left unused 3 Alarm output Delay Valve and Main Valve when defined will be allocated in this order right after t...

Страница 14: ...ered as a trigger for flushing The following flushing cycles will be triggered by the interval count down only The problem will be considered as solved when the constant indication of the DP sensor wi...

Страница 15: ...ER DP DELAY 30 seconds 5 ENTER LOOPING 10 6 ENTER ALARM No 7 ENTER DELAY VALVE No 8 ENTER VIEW OUTPUT No 9 ENTER Pressure PSI 10 ENTER BEEP Yes No set to No to prevent sign of life beep every 20 secon...

Страница 16: ...sure during Self Clean Solution Make sure water pressure during Self Clean is at least 40 psi Close the isolation valve on Outlet pipe of the HN G Press the M button on the Backwash Controller HN G wi...

Страница 17: ...Very Poor lines Water source should be rated at worst case scenario if water quality varies during the year such as algae blooms during summer A general guide to Water Quality is also shown below Good...

Страница 18: ...llation easier With unions at all recommended spots the filter may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed d...

Страница 19: ...mmodate low flow rate applications where all pressure and flow must be utilized for backwash the controlled outlet valve can also be applied in installation example A and C Pump Isolating valve Isolat...

Страница 20: ...strates a bypass configuration Union fitting Union fitting Pressure gauge Pressure gauge Piston 1 Hydraulic drain valve Union fitting Isolation valve Outlet to irrigation Inlet from pump Drain to drai...

Страница 21: ...TFC 10 06 Clamp MTFC 08 Cover MTFC 07 Hydraulic Motor MTFC 10 51 Collector Assembly MTFC 10 51 1 4 Tubing 6mm Plastic Tube MTFC Hex Nipple 1 MTFC Hex Nipple 1 CI010821W Streight Fitting 1 8 x 8mm MTFV...

Страница 22: ...22 1 Models 2 Models 1 2 1 2 7 1 8 7 1 4 22 13 16 25 5 8 9 15 16 10 9 16 6 7 1 16 G Dimensions 1 PVC SOCKET CONNECTION PESB SCRUBBER VALVE 12 1 8 REF 5 3 4 7 1 16 6 FILTER SERVICE AREA...

Отзывы: