B
Managed sensors
37
Table 14
shows the threshold definitions.
Supported sensors
Table 15
lists the sensors managed by the MMC.
Table 14. Threshold types
Threshold type
Description
UNR
Upper non-recoverable thresholds generate a critical alarm on the high side.
UC
Upper critical thresholds generate a major alarm on the high side.
UNC
Upper non-critical thresholds generate a minor alarm on the high side.
LNC
Lower non-critical thresholds generate a minor alarm on the low side.
LC
Lower critical thresholds generate a major alarm on the low side.
LNR
Lower non-recoverable thresholds typically generate a critical alarm on the low side.
Table 15. Managed sensors
Number
Name
Type
Reading
Type
Normal
Reading
Alarm
level
Notes
0
Hot Swap
Module
Hot Swap
Sensor
Specific
Discrete
N/A
N/A
Contains module hot swap information as defined in
the AMC.0 Specification
1
+3.3V MP
Voltage
Threshold
3.30
Minor,
Major,
Critical
This sensor measures voltage in Volts
Hysteresis: 0.05V
Default Thresholds
LNR
LC
LNC
UNC
UC
UNR
0.00
3.10
3.15
3.45
3.50
3.60
2
+12V
Voltage
Threshold
12.00
Minor,
Major,
Critical
This sensor measures voltage in Volts
Hysteresis: 0.10V
Default Thresholds
LNR
LC
LNC
UNC
UC
UNR
0.00
11.40
11.60
12.40
12.60
14.00
3
Outlet Temp Temp
Threshold
25
Minor,
Major,
Critical
This sensor measures temperature in °C
Hysteresis: 2°C
Default Thresholds
LNR
LC
LNC
UNC
UC
UNR
0
1
2
65
72
80
4
Inlet/HDD
Temp
Temp
Threshold
25
Minor,
Major,
Critical
This sensor measures temperature in °C
Hysteresis: 2°C
Default Thresholds
LNR
LC
LNC
UNC
UC
UNR
0
5
10
45
55
65