Page 65
© 2001 Radionics
D6412 Installation Guide
45349C
D6412
Appendix A
Enclosures
Radionics offers three optional enclosures for the control/communicator.
• The
D8103
enclosure is suitable for residential fire and/or burglary installations and commercial burglary
applications that do not require attack resistance or approval by Factory Mutual or NYC-MEA. (See the
Appendix
B: System Chart
for acceptable applications.)
• The
D8108A
is attack resistant. It is intended primarily for UL commercial burglar alarm and mercantile safe
and vault applications requiring a local bell. You can use the D8108A in any burglar or fire alarm application
where the 5591 or D8109 enclosure is suitable. UL lists the D8108A for all commercial fire alarm applications.
The D8108A is approved by Factory Mutual, California State Fire Marshal, and the New York City Materials and
Equipment Acceptance System.
• The
D8109
is normally used for commercial fire alarm applications. UL lists the D8109 for all commercial fire
alarm applications. The D8109 is approved by the California State Fire Marshal, NYC-MEA and FM.
IMPORTANT
All references to NFPA and related requirements are based upon compliance with the 1993 edition of NFPA
72, National Fire Alarm Code. Since installation specifications are nearly always based upon a specific
edition of a standard which has been legally adopted by the Authority Having Jurisdiction (AHJ), earlier
editions of NFPA standards will generally apply. Consult with the appropriate AHJ for confirmation.
Appendix A: System Chart
Household Burglary (Grade A)
Household Fire
Household Fire/Burglary Combined
Central Station Burglary (Grade C)
Police Connected Burglary
Local Burglary
Mercantile (4 hrs) Commercial
Mercantile (72 hrs) Bank Safe/Vault Alarm
Proprietary Burglary
NFPA Standard
72
72
Min. Hrs of Standby
Battery
4
4 hrs +
24 min
4 hrs +
24 min
4
4
4
4
72
4
Entry/Exit Time (sec)*
45/60
45/60
45/60
60/60
60/60
60/60
60/60
60/60
60/60
Bell Time (minutes)
4
4
4
15
15
15
15
15
15
D2203 Enclosure
Included w/ panel
No
No
No
No
No
No
D8103 Enclosure**
Optional
No
No
No
No
No
D8108A Enclosure
Optional
Req
Req
Req
Req
Req
D8109 Enclosure
Optional
Choose
One
No
No
No
No
No
D126 Battery (7 Ah)
Req
Req
Req
Req
Req
Req
Req
No
Req
D1218 Battery (18 Ah)
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Req
Opt
D127 Reversing Relay
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
D132A Smoke
Detector Reversing
Relay Module
Required if D192C is not used. Use the D132A with compatible smoke detectors only.
D164 Telephone Cord
Required to connect panel to RJ131X Telco Block.
D192C NAC
Supervision Module
Required if D132A and compatible smoke detectors
are not used.
D621, D623, D625
Command Center
1+
1+
1+
1+
1+
1+
1+
1+
1+
D262 Smoke Detector
Head/D261 Base
1
•
1
•
D282THS Smoke
Detector w/ Sounder
Use with D132A.
D431, D440, D442,
D448 Indicating
Device
1+
1+
1+
Opt
♦
♦
♦
♦
♦
D1825 Transformer
Required for all applications.
D8004 Transformer
Enclosure
Opt
Opt
Opt
Opt
Opt
Opt
D8122 Derived
Channel STU
Optional. Contact Telco availability of derived channel
service.
D8130 Release
Module
Optional
Key
No
Not acceptable for this
application.
Req
Required for this
application.
Opt
Optional for this
application.
1+
1 or more required for this
application. Consult the
appropriate standard.
2+
2 or more required for this
application. Consult the
appropriate standard.
1
•
At least one detector
required. You can
substitute other 2-wire
detectors listed for use
with the D6412. You could
use the D262 with the
D270 4-wire base or
other manufacturer's 4-
wire detectors. You must
use a listed power
supervision relay with 4-
wire detectors.
♦
UL Listed bell (siren)
housing required for
burglary alarm bell or
siren (Rothenbuhler 5110
Bell).
Empty Cell
Not used for this
application.
∗
Not to exceed these
Entry/Exit Delay limits for
UL installations.
∗∗
D101 used for this
application.