Page 60
45349C
© 2001 Radionics
D6412 Installation Guide
D6412
Quick Terminal Reference Description
15.0 Quick Reference Terminal Description
Term
Silkscreen
(below terminals)
Description
1,2
18 VAC
18 V, 22 VA; up to 50 ft. (15.3 m), #18 AWG (1.2 mm), Stranded.
3
Earth Ground Symbol
Earth Ground.
4
Data, Grn (Green)
SDI data on Terminals 4 &5. Panel supports up to 1,000 ft. (305 m) of #22 AWG (0.8 mm) wire on these terminals
(any configuration).
5
Data, Yel (Yellow)
6,7
Aux Power 12 VDC (-)
Terminals 6-9 are Aux power. 600 mA. Include any programmable outputs (PO 1 to PO 4) not configured for alarm
output. PTC protected.
8,9
Aux Power 12 VDC (+)
JP3
Aux/Data (RYGB)
4-pin connector to Data bus and Aux power. Use to connect an installer keypad for keypad programming.
Red (Bat +)
Battery (+) spade.
Black (Bat -)
Battery (-) spade.
10
PO 4
Programmable Output, up to 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions. PTC
protected.
11
PO 3
Programmable Output, up to 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions. PTC
protected.
12
PO 2
Programmable Output. 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions.
Supervised for Horn/Speaker alarm function. PTC protected.
13
Alrm +
Alarm power. Up to 1,850 mA. PTC protected. Provides power for supervised siren driver (PO 2) and Alarm Output
(PO 1).
14
PO 1, A
Jumper sets PO 1 terminals A (14) and B (15) for 'dry' Form "A" contact or for Alarm Output.
15
PO 1, B
16
L-1 (+)
Positive terminal of powered loop. Supports up to 15 D263THS smoke detectors (D132A Reversing Module
required). PTC protected.
17
L-1 (-)
Negative terminal of powered loop.
18
Com
Common for Sensor Loop 2.
19
L-2
Sensor Loop 2 input. Wire length for Sensor Loops 2 to 8 are limited only by the resistance on the loop and potential
EMI problems. Resistance must be < 100 W with EOL resistor shorted and detection devices connected.
20
L-3
Sensor Loop 3 input.
21
Com
Common for Sensor Loops 3 and 4.
22
L-4
Sensor Loop 4 input.
23
L-5
Sensor Loop 5 input.
24
Com
Common for Sensor Loops 5 and 6.
25
L-6
Sensor Loop 6 input.
26
L-7
Sensor Loop 7 input.
27
Com
Common for Sensor Loops 7 and 8.
28
L-8
Sensor Loop 8 input.
29
T
Tip of telephone line.
30
T1
Tip of house (premises) phones.
31
R1
Ring of house (premises) phones.
32
R
Ring of telephone line.
JP2, PO1 Select
æ
Configures PO 1 for Form "A" relay or Alarm Output.
Auxiliary
Auxiliary Module and/or Programming Key Header.
Installer