D6412 Installation Guide
D6412
Troubleshooting
16.1.4 Programming Issues
•
Problem:
I cannot enter into programmer’s mode.
•
Cause:
One or more areas are armed; programming may be disabled; the Installer’s Switch may be
open.
•
Solution:
- If one or more areas are armed, disarm all armed areas. Programmer’s mode cannot be entered
while one or more areas are armed.
-
Programming may be disabled. See Section 2.5
Programming Options
,
Installer Switch and Daylight
Savings Time Options
(Nibble 0257) in the
D6412 Program Entry Guide
(P/N: 45351). Make sure
the following options are enabled: Installer Switch, Keypad Programming and PK32 (Programming
Key).
- To enter the programmer’s mode, the Installer Switch must be closed. See the following section in
this installation guide for details: 3.5.2,
Closing the Installer Switch,
and 13.2,
Entering the Installer
Mode
.
•
Problem:
I have enabled Open/Close reports, but when I arm the panel Part On, these reports are still not sent.
•
Cause:
The Open/Close reports for Part On modes is not programmed correctly.
•
Solution:
In the
D6412 Program Entry Guide
(P/N: 45351), Section 2.7
Areas
, see the
Area # Opening/
Closing Reporting Options
parameter. Enable “Opening/Closing Reports for Part On Modes” for Nibbles
0296, 0318, 0340 and 0362.
•
Problem:
The PK32 (Programming Key) does not work (upload, download, erase, etc.).
•
Cause:
The PK32 has not been enabled in the panel firmware.
•
Solution:
In Nibble 0257, enable the PK32. See the
D6412 Program Entry Guide
(P/N: 45351), Section
2.5
Programming Options.
•
Problem:
The off-board points I added to the system display as missing.
•
Cause:
The device location parameter is not correctly programmed.
•
Solution:
See Section 2.13
Locations
in the
D6412 Program Entry Guide
(P/N: 45351)
.
Verify which
device type has been added (for example, RF point, off-board point, etc.). In the Device Location parameter,
enter in the correct value based on the Device Parameter Selections (1 = on-board; 2 = D9528; 3 =
D9528, Doubled; 4 = RF Receiver 1; 5 = RF Receiver 2). Point configuration is locked into only those
configuration types in the Device Parameter Selections.
•
Problem:
The panel does not send a Closing report after it is armed Part On.
•
Cause:
Open/Close reports for Part On mode are not enabled.
•
Solution:
See Section 2.7
Areas
in the
D6412 Program Entry Guide
(P/N: 45351). In the
Area # Opening/
Closing Reporting Options
parameter, enable “Open/Close Reports for Part On Modes” by entering a 4,
5, 6, 7 or 12, 13, 14 or 15 in the appropriate Nibble (0296, 0318, 0340, or 0362).
•
Problem:
There are numbers in brackets [###] throughout the
D6412 Program Entry Guide
(P/N: 45351).
•
Cause:
These numbers [###] refer to the event numbers described in Appendix B of the
D6412 Program
Entry Guide
(P/N: 45351).
•
Problem:
There is no output after alarming a point.
•
Solution:
Review the following sections in the
D6412 Program Entry Guide
(P/N: 45351): 2.17
Outputs
and 2.14
Point Index Configuration, Point Index Option 2
.