background image

D2212 Installation Manual

Page  10

© 1996 Radionics

74-07361-000-C 11/11/96

Lead Acid Batteries Only: The panel charging circuit is
only calibrated for lead-acid batteries. Do not use gel-cell or
nicad batteries.

Battery Replacement

Radionics recommends battery replacement every three to
five years under normal use. Exceeding the maximum output
ratings, or installing the transformer in an outlet that is
routinely switched off, causes heavy discharges. Routine
heavy discharges can lead to premature battery failure.

D135A Prevents Deep Discharge: The D135A Low Battery
Cutoff Module protects the battery from deep discharge
during extended power outages. Deep discharge can cause
permanent battery damage.

Battery Supervision

When the battery drops to 12.1 VDC, the keypad indicates a
trouble condition. The panel will transmit a BATTERY LOW
report.

When battery voltage returns to 13.0 VDC and there is AC
power at terminals 1 and 2, the keypad returns to normal
operation. The panel will transmit a BATTERY RESTORAL
report.

Investigate low battery reports right away:  If primary
(AC) power is off and the discharge continues, the panel
becomes inoperative when the battery voltage drops below
10.2 VDC.

If  the battery is disconnected, it takes 60 seconds for the
panel to recognize the condition.

Battery Charging Circuit Float Charge

The float voltage for the battery charging circuit is 13.9 VDC.
Deduct any continuous load for devices connected to the
panel from 1.0 A to find the maximum current available for
charging. At 13.9 VDC, the battery is fully charged and is
maintained with a trickle charge of approximately 5.0mA.

Battery Discharge/Recharge Schedule (No AC Power)

Discharge Cycle

AC OFF

The keypad indicates trouble
AC Fail reports if programmed

13.9 VDC

Charging float level

12.1 VDC

Low Battery reports

10.2 VDC

Panel stops processing below 10.2 VDC

Recharge Cycle

AC ON

Panel restarts, battery charging begins,
AC restoral report sent

13.0 VDC

Battery restoral reports sent,  the keypad
returns to normal operation

13.9 VDC

Battery float charged

Fill out the Point Chart

Radionics recommends that you fill out the 

Point Chart on

the Installation Label located on the inside of the D2203
Enclosure cover.

You must fill out the point chart if you programmed
Point 1 for Fire with Verification (Digit 1 = 2). 
See POINT
CODES in the D2212 Program Entry Guide for more
information.

Use the 

Program Record Sheet to gather the information you

need to fill out the point chart.

Test the System

After finishing the installation and programming, perform a
complete functional test of the system. Test the panel and all
devices for proper operation. Test after you first program the
panel and after any subsequent programming sessions.

Clear after test:  To clear the alarm memory and report
buffer, place the Standby Switch in the closed position for
two seconds and then release it. The panel returns to
service in the disarmed state.

Detailed Panel Description

Primary (AC) Power Circuit

A 16.5 VAC, 40VA transformer (Radionics model D1640) is
the primary power source for the panel.

The AC power circuit provides 1.5 Amps of rectified DC
power. The panel reserves 140mA of this power for internal
operations and 1.0 A for continuously powered devices.
Under alarm conditions, 1.0 A of power is available for
continuously powered and alarm indicating devices
combined.

Transient suppressors and spark gaps protect the circuit
from power surges. This protection relies on the ground
connection at terminal 3. Make sure you connect terminal 3
to a proper ground.

AC Power Failure

The panel indicates an AC power failure when power at
terminals 1 and 2 is missing for 60 seconds. The 

AC Fail

Buzz/Rpt

  

program item sets the panel response to detected

AC failure. The panel indicates an AC power restoral 60
seconds after power restores to terminals 1 and 2.

Secondary (DC) Power

A 12V, 7.0 Ah sealed lead-acid rechargeable battery
(Radionics D126) supplies secondary power for auxiliary and
alarm outputs. The battery also powers the system during
interruptions in primary (AC) power.

www.PDF-Zoo.com

firealarmresources.com

Содержание D2212

Страница 1: ...74 07361 000 C 11 11 96 1995 1996 Radionics D2212 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone line Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 Contact the telephone comp...

Страница 3: ...es the following D222 Text Keypad with Point Expansion 4 points Installation Sheet 74 07362 000 User s Reference Card 71 04523 010 Security System User s Guide 71 07374 000 Getting Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Six wire point cable assembly 15 07251 000 Four 1k Ω end of line resistors 30 01098 102 Table of Contents Introduction 3 D2212 Cont...

Страница 4: ...ing Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Battery Order a D126 Battery 12 V 7 0Ah to complete a basic D2212 installation Enclosure Options The D2212 is shipped in the D2203 enclosure If you want to mount the D2212 in one of the optional enclosures listed below order the D2212M and the enclosure of your choice D8103 Universal Enclosure D8108A Attack...

Страница 5: ...wire maximum under the terminal Use a spade lug or splice for larger wire Do not connect any other panel terminals to earth ground The panel s common terminals and terminal 3 earth ground are electrically isolated Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel W...

Страница 6: ...using Point 1 as a fire point the number of detection devices you can connect to its sensor loop is limited See Point 1 on Page 7 The number of detection devices you can connect to the sensor loops for points 2 to 8 is limited only by the resistance on the loop Resistance must be less than 100Ω with the detection devices connected Continue Connections to the Panel Power Down First Unplug the trans...

Страница 7: ...onnections Warning Do not connect wiring for external devices directly to terminals 11 or 12 Install D133 D134 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1 The D133 draws 36mA when energized When both relays are energized the D134 draws 72 mA Connect the Points On Board Points Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered supervised ...

Страница 8: ...oint wiring Four Wire Smoke Detectors Connect any number limited by available power and the Authority Having Jurisdiction of 12 VDC four wire smoke detectors to any supervised point Install a suitable power supervision device according the manufacturer s instructions Route the power for the detectors through a D133 D134 Relay Module The relay module must be connected to one of the panel s external...

Страница 9: ...dular Phone Jack Premises Phone RJ31X Module Figure 6 RJ31X Phone Jack Program Entry Guide for programming options and keypad programming instructions If you re programming from the keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programmer Operation Manual for instruction...

Страница 10: ...0 VDC Battery restoral reports sent the keypad returns to normal operation 13 9 VDC Battery float charged Fill out the Point Chart Radionics recommends that you fill out the Point Chart on the Installation Label located on the inside of the D2203 Enclosure cover You must fill out the point chart if you programmed Point 1 for Fire with Verification Digit 1 2 See POINT CODES in the D2212 Program Ent...

Страница 11: ...ch the receiver 10 attempts if two phone number are programmed the panel goes into communication failure The panel clears any reports in its phone buffer The panel sounds a tone at the keypad indicating trouble Pressing the Clear key silences the tone When communication restores a report is acknowledged by the receiver the keypad returns to normal operation Ground Start Some telephone systems requ...

Страница 12: ...Shorted Loop Greater than 0 0 VDC but less than 2 0 VDC Points 7 and 8 Points 7 and 8 are not supervised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans one second before the panel initiates an alarm...

Страница 13: ...5 minutes for Commercial Burglary applications For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed Enclosures The D2203 enclosure is suitable for Household Fire and Burglary applications only Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications Radionics offers three opt...

Страница 14: ...electronic vibration sensor directly inside the metal cabinet of the D8108A Do NOT install the sensor within a quarter inch 1 4 of the components or traces of the printed circuit assembly System Chart Household Burglar Grade A Household Fire Household Fire Burglary Combined Central Station Burglary Grade C Police Connected Burglary Local Burglary Proprietary Burglary NFPA Standard 72 72 Min Hours ...

Страница 15: ...es System Wiring Diagram Issue A s s P P P D164 Phone Cord to RJ31X for Phone Line Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns P P P P D133 D134 Relay P P Supervised with 1k Ω EOL Resistor Typical Initiating Devices are Door Contacts NO NC Floor Mats Motion Sensors Glass Break Detectors etc NOT Supervised Normally Closed Typical Initiating Devices are ...

Страница 16: ...moke Detector Head D208 RF Receiver D216 RF Receiver Radionics Inc 1800 Abbott Street Radionics 1 Park Gate Close Bredbury Salinas California 93901 Stockport Cheshire SK6 2SZ England Customer Service 800 538 5807 Technical Support 061 494 0851 The Radionics logo is a registered trademark of Radionics Inc Salinas CA U S A 1995 Radionics Inc Salinas CA U S A All rights reserved D2212 Terminal Quick ...

Отзывы: