Specifications

Primary Power Supply

16.5 VAC, 40 VA class 2 plug-in transformer (D1640)

Secondary Power Supply

12 VDC, 7.0 Ah sealed lead acid rechargeable battery.

Auxiliary Power Output

1 A maximum at 10.2 VDC to 13.9 VDC for devices powered at
terminal 9 (140mA for Fire and combined Fire/Burglary systems).

Alarm Power Output

1.85 A maximum at 10.2 VDC to 13.9 VDC output. Output may
be steady or pulsed depending on programming.

Fire and Fire/Burglary Systems
To comply with UL 985 listing standards for household fire alarm
systems, the total combined continuous and alarm current draw
for the system during alarm conditions must be limited to 860
mA provided by the primary power supply (rectified AC).

Operating Voltage

10.2 VDC (minimum)

13.9VDC (maximum)

Telephone Connection

RJ31X or RJ38X jack interfaced with D164 phone cord.

Environmental

Temperature: 32

°

-122

°

F (0

°

-50

°

C)

Relative Humidity:  5-85% at 86

°

F (30

°

C) non-condensing

D2203 Enclosure Dimensions
Height: 14.75 inches, Width: 12.75 inches, Depth: 3.5 inches

Arming Stations

D202A Keypad, D220A Keypad, D222 Keypad, D223 Keypad

D204RF Keypad

Keyswitch

Easikey

Compatible Enclosures

D2203 or D8103 Universal Enclosures

D8109 Fire Enclosure

D8108A Attack Resistant Enclosure

Compatible Accessories (see Radionics catalog for complete list)

D126 12V, 7 Ah Rechargeable Battery

D127 Reversing Relay

D132 Smoke Detector Reversing Relay Module

D133 Relay Module

D134 Dual Relay Module

D135A Low Battery Cutoff Module (not UL listed)

D164 Phone Cord

D192C Bell Supervision Module

D202A Keypad

D204RF Keypad (not UL listed)

D208 8-Point Expansion Module

D220A Keypad

D222 Keypad

D223 Keypad

D250 Heat Detector Base

D254 135

°

 Heat Detector Head

D255 190

°

 Heat Detector Head

D440 (6"), D442 (10") Bells

D448 12 VDC Horn

D1640 16.5 VAC 40 VA Transformer

D5200 Programmer

D5300 Remote Account Manager II

D8004 Transformer Enclosure

D8121A/D8122 Derived Channel S.T.U. (D8122 for UL systems)

Easikey (not for use in UL systems)

D261A Smoke Detector Base

D262 Smoke Detector Head

D208 RF Receiver

D216 RF Receiver

Radionics, Inc., 1800 Abbott Street

Radionics,  1 Park Gate Close, Bredbury

Salinas, California 93901

Stockport, Cheshire, SK6 2SZ, England

Customer Service: (800) 538-5807

Technical Support: (061) 494 0851

The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, U.S.A. ©1995 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved

D2212 Terminal Quick Reference

Terminal

Description

1,2

AC Input

Connect 16.5 VAC, 40 VA transformer for
primary power source.

3

Earth Ground

Connect to earth ground. A cold water
pipe or grounding rod is preferred.
Do not connect to telephone or electrical
ground.

4

Battery
Positive

Connect  Positive terminal of 7.0 Ah
battery to this terminal.

5

Battery
Negative

Connect  Negative terminal of 7.0 Ah
battery to this terminal

6

Alarm Output
Positive

Supplies 1.85 Amps at 10.2 to 13.9 VDC
for alarm output.
This terminal provides a constant output.
Negative is switched.

7

Alarm Output
Negative

Negative terminal for alarm output. This
terminal switches for pulsed or steady
alarm output.

8

Data

Data for Keypads, RF Receivers, etc.

9

Auxiliary Power
Positive

One Amp at 10.2 to 13.9 VDC for
auxiliary power, keypads, and relay
outputs.

10

Common

Common for Auxiliary Power and Relay
Drivers.

11

External
Relay 1

Connect D133/D134 Relay for Form C
Dry Contact.

12

External
Relay 2

Connect D133/D134 Relay for Form C
Dry Contact.

13

Positive
Point 1

Positive power for Point 1. Switched for
sensor reset.
Use approved 2-wire smoke or glass
break detectors.

14

Negative
Point 1

Negative power for Point 1.

15

Common

Common for Point 2.

16

Input Point 2

Input for Point 2.

17

Input Point 3

Input for Point 3.

18

Common

Common for Points 3 and 4.

19

Input Point 4

Input for Point 4.

20

Input Point 5

Input for Point 5.

21

Common

Common for Points 5 and 6.

22

Input Point 6

Input for Point 6.

23

Input Point 7

Input for Point 7 (no EOL resistor).

24

Common

Common for Points 7 and 8.

25

Input Point 8

Input for Point 8. No EOL Resistor.

26

T1

Tip of phone line to  premises phone.

27

T

Tip of  incoming phone line.

28

R

Ring of incoming phone line.

29

R1

Ring of phone line to premises phone.

www.PDF-Zoo.com

firealarmresources.com

Содержание D2212

Страница 1: ...74 07361 000 C 11 11 96 1995 1996 Radionics D2212 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone line Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 Contact the telephone comp...

Страница 3: ...es the following D222 Text Keypad with Point Expansion 4 points Installation Sheet 74 07362 000 User s Reference Card 71 04523 010 Security System User s Guide 71 07374 000 Getting Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Six wire point cable assembly 15 07251 000 Four 1k Ω end of line resistors 30 01098 102 Table of Contents Introduction 3 D2212 Cont...

Страница 4: ...ing Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Battery Order a D126 Battery 12 V 7 0Ah to complete a basic D2212 installation Enclosure Options The D2212 is shipped in the D2203 enclosure If you want to mount the D2212 in one of the optional enclosures listed below order the D2212M and the enclosure of your choice D8103 Universal Enclosure D8108A Attack...

Страница 5: ...wire maximum under the terminal Use a spade lug or splice for larger wire Do not connect any other panel terminals to earth ground The panel s common terminals and terminal 3 earth ground are electrically isolated Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel W...

Страница 6: ...using Point 1 as a fire point the number of detection devices you can connect to its sensor loop is limited See Point 1 on Page 7 The number of detection devices you can connect to the sensor loops for points 2 to 8 is limited only by the resistance on the loop Resistance must be less than 100Ω with the detection devices connected Continue Connections to the Panel Power Down First Unplug the trans...

Страница 7: ...onnections Warning Do not connect wiring for external devices directly to terminals 11 or 12 Install D133 D134 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1 The D133 draws 36mA when energized When both relays are energized the D134 draws 72 mA Connect the Points On Board Points Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered supervised ...

Страница 8: ...oint wiring Four Wire Smoke Detectors Connect any number limited by available power and the Authority Having Jurisdiction of 12 VDC four wire smoke detectors to any supervised point Install a suitable power supervision device according the manufacturer s instructions Route the power for the detectors through a D133 D134 Relay Module The relay module must be connected to one of the panel s external...

Страница 9: ...dular Phone Jack Premises Phone RJ31X Module Figure 6 RJ31X Phone Jack Program Entry Guide for programming options and keypad programming instructions If you re programming from the keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programmer Operation Manual for instruction...

Страница 10: ...0 VDC Battery restoral reports sent the keypad returns to normal operation 13 9 VDC Battery float charged Fill out the Point Chart Radionics recommends that you fill out the Point Chart on the Installation Label located on the inside of the D2203 Enclosure cover You must fill out the point chart if you programmed Point 1 for Fire with Verification Digit 1 2 See POINT CODES in the D2212 Program Ent...

Страница 11: ...ch the receiver 10 attempts if two phone number are programmed the panel goes into communication failure The panel clears any reports in its phone buffer The panel sounds a tone at the keypad indicating trouble Pressing the Clear key silences the tone When communication restores a report is acknowledged by the receiver the keypad returns to normal operation Ground Start Some telephone systems requ...

Страница 12: ...Shorted Loop Greater than 0 0 VDC but less than 2 0 VDC Points 7 and 8 Points 7 and 8 are not supervised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans one second before the panel initiates an alarm...

Страница 13: ...5 minutes for Commercial Burglary applications For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed Enclosures The D2203 enclosure is suitable for Household Fire and Burglary applications only Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications Radionics offers three opt...

Страница 14: ...electronic vibration sensor directly inside the metal cabinet of the D8108A Do NOT install the sensor within a quarter inch 1 4 of the components or traces of the printed circuit assembly System Chart Household Burglar Grade A Household Fire Household Fire Burglary Combined Central Station Burglary Grade C Police Connected Burglary Local Burglary Proprietary Burglary NFPA Standard 72 72 Min Hours ...

Страница 15: ...es System Wiring Diagram Issue A s s P P P D164 Phone Cord to RJ31X for Phone Line Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns P P P P D133 D134 Relay P P Supervised with 1k Ω EOL Resistor Typical Initiating Devices are Door Contacts NO NC Floor Mats Motion Sensors Glass Break Detectors etc NOT Supervised Normally Closed Typical Initiating Devices are ...

Страница 16: ...moke Detector Head D208 RF Receiver D216 RF Receiver Radionics Inc 1800 Abbott Street Radionics 1 Park Gate Close Bredbury Salinas California 93901 Stockport Cheshire SK6 2SZ England Customer Service 800 538 5807 Technical Support 061 494 0851 The Radionics logo is a registered trademark of Radionics Inc Salinas CA U S A 1995 Radionics Inc Salinas CA U S A All rights reserved D2212 Terminal Quick ...

Отзывы: