D2212 Installation Manual

Page  14

© 1996 Radionics

74-07361-000-C 11/11/96

Standby Battery Requirements

Household Burglary and Commercial Burglary

Four hours of standby battery capacity required.

Standby Battery Calculation for Fire Alarm Applications

NFPA 72 (Ch. 2) Household Fire Warning Equipment

The NFPA 72 (Chapter 2) Household Fire Warning
Equipment Standard requires 24 hours of s 4 min.
(.067 hrs) of alarm operation at the end of the 24 hr. period.

You must use battery ampere hour (Ah) calculations to verify
compliance. The formula below  includes a 10% contingency
factor for depletion of battery capacity with age.

NFPA 72 (Ch. 2) Ampere-Hour Calculation Formula
(Total B ___  x 24 Hrs) + (Total C ___  x .067 Hrs) +

(10%

 Contingency)  = Total Ah required.

Total Ah requirements must not exceed Ah capacity of
batteries.

The D2212 control panel is suitable for Proprietary Burglar Alarm,
Grade C applications. Also suitable for Proprietary Burglar Alarm,
Grade B applications when the Model D2212 DACT unit is installed
with a UL Listed local sounding device. Also suitable for Proprietary
Burglar Alarm, Grade AA when the Model D2212 DACT is installed
with the Model D8122 derived channel subscriber terminal unit.

The D2212 control panel is suitable for Household, Grade A
applications.
UL Standard 681 for Installation and Classification of Mercantile and
Bank Burglary Alarm systems requires foil lining or equivalent
protection of the control unit enclosure. The D8108A enclosure does
not have a foil lining, but acceptable protection can be provided by
mounting listed electronic vibration sensors inside the enclosure.
Proximity alarms (capacitance) cannot be used for this
purpose
.

Install electronic vibration sensors in the D8108A enclosure that are
identical to those used to protect the safe or vault. Sentrol 5402,
Potter EVD-S, or Arrowhead S-3810 electronic vibration detection
(EVD) systems which can be mounted inside the enclosure meet the
requirements of UL 681. Mount the electronic vibration sensor
directly inside the metal cabinet of the D8108A. Do NOT install the
sensor within a quarter inch (1/4”) of the components or traces of the
printed circuit assembly.

System Chart

Household Burglar

(Grade A)

Household Fire

Household Fire/

Burglary Combined

Central Station

Burglary (Grade C)

Police Connected

Burglary

Local Burglary

Proprietar

y

 Bur

g

lar

y

NFPA Standard

72

72

Min. Hours of Standby
Battery

4

24 +

4 min

alarm

24 +

4 min

alarm

4

4

4

4

D2203 Enclosure

Included with panel

No

No

No

D8103 Enclosure

Optional

*

No

No

No

D8108A Enclosure

Optional

Choose

Req.

Req.

Req.

D8109 Enclosure

Optional

One

No

No

No

D126 Battery

1

1

1

1

1

1

1

D127 Reversing Relay

Opt.

No

Opt.

Opt.

Opt.

Opt.

Opt.

D164 Telephone Cord

Required to connect panel to RJ31X Telco Block

D205, D206 Command
Center

1+

1+

1+

1+

1+

1+

1+

D262 Smoke Detector Head
D261 Base

1•

1•

D431, D435, D438, D440,
D442, D448 Indicating
Device

1+

1+

1+

Opt.

u

u

u

D133, D134 Relays

Opt.

Opt.

Opt.

Opt.

Opt.

Opt.

Opt.

D1640 Transformer

Required for all applications

D8004 Transformer
Enclosure

Opt.

Opt.

Opt.

Opt.

Opt.

Opt.

D8122 Derived Channel
S.T.U.

Opt. Contact TelCo for availability of derived channel service

D8130 Release Module

Optional

The D2212 is not listed for these applications:  Local Fire/Burglary Combined, Local Fire, Local and
Central Station Fire Combined, Local and Central Station Fire/Burglary (Grade C), Central Station
Fire/Burglary (Grade C), Central Staion Fire, and Electrically Actuated Transmitter.

Key

No

=

Not acceptable for this
application.

Req

=

Required for this
application.

Opt.

=

Optional for this application.

1+

=

One or more required for
this application. Consult the
appropriate standard.

2+

=

Two or more required for
this application. Consult the
appropriate standard.

1•

=

At least one detector
required. You can substitute
other 2-wire detectors
listed for use with the
D2212. You could use the
D262 with the D270 4-wire
base or other
manufacturer’s 4-wire
detectors. You must use a
listed power supervision
relay with 4-wire detectors.

u

=

Listed bell (siren) housing
required for burglary alarm
bell or siren.

¨

=

(Empty Box) Not used with
this application.

*

=

D101 required for D8103
enclosure.

www.PDF-Zoo.com

firealarmresources.com

Содержание D2212

Страница 1: ...74 07361 000 C 11 11 96 1995 1996 Radionics D2212 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone line Excessive RENs on the telephone line may result in devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 Contact the telephone comp...

Страница 3: ...es the following D222 Text Keypad with Point Expansion 4 points Installation Sheet 74 07362 000 User s Reference Card 71 04523 010 Security System User s Guide 71 07374 000 Getting Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Six wire point cable assembly 15 07251 000 Four 1k Ω end of line resistors 30 01098 102 Table of Contents Introduction 3 D2212 Cont...

Страница 4: ...ing Started w Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 Battery Order a D126 Battery 12 V 7 0Ah to complete a basic D2212 installation Enclosure Options The D2212 is shipped in the D2203 enclosure If you want to mount the D2212 in one of the optional enclosures listed below order the D2212M and the enclosure of your choice D8103 Universal Enclosure D8108A Attack...

Страница 5: ...wire maximum under the terminal Use a spade lug or splice for larger wire Do not connect any other panel terminals to earth ground The panel s common terminals and terminal 3 earth ground are electrically isolated Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel W...

Страница 6: ...using Point 1 as a fire point the number of detection devices you can connect to its sensor loop is limited See Point 1 on Page 7 The number of detection devices you can connect to the sensor loops for points 2 to 8 is limited only by the resistance on the loop Resistance must be less than 100Ω with the detection devices connected Continue Connections to the Panel Power Down First Unplug the trans...

Страница 7: ...onnections Warning Do not connect wiring for external devices directly to terminals 11 or 12 Install D133 D134 modules connected to terminals 11 and 12 in the enclosure with the panel as shown in Figure 1 The D133 draws 36mA when energized When both relays are energized the D134 draws 72 mA Connect the Points On Board Points Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered supervised ...

Страница 8: ...oint wiring Four Wire Smoke Detectors Connect any number limited by available power and the Authority Having Jurisdiction of 12 VDC four wire smoke detectors to any supervised point Install a suitable power supervision device according the manufacturer s instructions Route the power for the detectors through a D133 D134 Relay Module The relay module must be connected to one of the panel s external...

Страница 9: ...dular Phone Jack Premises Phone RJ31X Module Figure 6 RJ31X Phone Jack Program Entry Guide for programming options and keypad programming instructions If you re programming from the keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programmer Operation Manual for instruction...

Страница 10: ...0 VDC Battery restoral reports sent the keypad returns to normal operation 13 9 VDC Battery float charged Fill out the Point Chart Radionics recommends that you fill out the Point Chart on the Installation Label located on the inside of the D2203 Enclosure cover You must fill out the point chart if you programmed Point 1 for Fire with Verification Digit 1 2 See POINT CODES in the D2212 Program Ent...

Страница 11: ...ch the receiver 10 attempts if two phone number are programmed the panel goes into communication failure The panel clears any reports in its phone buffer The panel sounds a tone at the keypad indicating trouble Pressing the Clear key silences the tone When communication restores a report is acknowledged by the receiver the keypad returns to normal operation Ground Start Some telephone systems requ...

Страница 12: ...Shorted Loop Greater than 0 0 VDC but less than 2 0 VDC Points 7 and 8 Points 7 and 8 are not supervised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans one second before the panel initiates an alarm...

Страница 13: ...5 minutes for Commercial Burglary applications For all Commercial Burglary applications the system must be programmed to sound the audible device every time the system is armed Enclosures The D2203 enclosure is suitable for Household Fire and Burglary applications only Enclosure tamper protection causing an immediate alarm signal is required for all burglary applications Radionics offers three opt...

Страница 14: ...electronic vibration sensor directly inside the metal cabinet of the D8108A Do NOT install the sensor within a quarter inch 1 4 of the components or traces of the printed circuit assembly System Chart Household Burglar Grade A Household Fire Household Fire Burglary Combined Central Station Burglary Grade C Police Connected Burglary Local Burglary Proprietary Burglary NFPA Standard 72 72 Min Hours ...

Страница 15: ...es System Wiring Diagram Issue A s s P P P D164 Phone Cord to RJ31X for Phone Line Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns P P P P D133 D134 Relay P P Supervised with 1k Ω EOL Resistor Typical Initiating Devices are Door Contacts NO NC Floor Mats Motion Sensors Glass Break Detectors etc NOT Supervised Normally Closed Typical Initiating Devices are ...

Страница 16: ...moke Detector Head D208 RF Receiver D216 RF Receiver Radionics Inc 1800 Abbott Street Radionics 1 Park Gate Close Bredbury Salinas California 93901 Stockport Cheshire SK6 2SZ England Customer Service 800 538 5807 Technical Support 061 494 0851 The Radionics logo is a registered trademark of Radionics Inc Salinas CA U S A 1995 Radionics Inc Salinas CA U S A All rights reserved D2212 Terminal Quick ...

Отзывы: