3. Installation
3.1. General warnings
TKAN boilers are intended for the maximum working pressure of 3 bars and
maximum working temperature of 90°C, therefore they fit into the category of hot water
boilers. Operating at higher values than listed can cause great material damages and
endanger human lives.
It is strictly forbidden to reduce the cross-sections of safety lines. Also, it is strictly
forbidden to install safety equipment whose working pressure is higher than 3 bar. It is
recommended to install a thermal leakage valve in accordance with the law of the country
in which the equipment is installed.
The boiler has the fan, automatic controls system, the pellets transport mechanism
eventually the furnace or pipe bundle cleaning mechanism. All these devices use a 230V
or 3x380V power supply, therefore improper installation and careless handling can
endanger human life by electrocutionThe boiler has the fan, automatic controls system,
the pellets transport mechanism eventually the furnace or pipe bundle cleaning
mechanism. All these devices use a 230V or 3x380V power supply, therefore improper
installation and careless handling can endanger human life by electrocution.
During each intervention on the boiler’s electric system (e.g. changing electric
heater for firing, electric gear motor interventions or fan interventions, etc.) it is
mandatory to shut down the main power supply by disconnecting the socket from the
network installation. This way, possible electric shocks and endangering lives of
technicians performing the intervention are avoided.
Solid fuel and forced draft boiler should be installed according to valid norms and
law regulations. Every change either on the mechanical construction or on the electrical
installation will be considered a violation of warranty terms and lead to their violation.
Before initiating the boiler, make sure that the direction of a pellets feeder
system’s motor is such that it provides pellets supply into the furnace. Also, if a power
outage happens while using generators, check if the direction of the motor is such that
pellets go directly into the firing chamber. On the contrary, permanent boiler damages
may occur.