Figure 9.2 Installation of flue gas channels and fresh air inlet for combustion
The BIOlux UNI 20 boiler operates under forced draft conditions with one fan, but the rules
for the selection of a chimney should be respected as if it was intended for the boiler with a mild
sub-pressure in the firebox working on another fuel type, such as fuel oil. The chimney cross
section should be 130mm, otherwise it may cause problems in the process of operation.
It is recommended for the chimney diameter to be larger than the diameter of a flue outlet.
Arches should be avoided if possible; if not, the maximum number of arches should be 2. It is
desirable to isolate the flue gas channel running from a boiler to a chimney, particularly if there
are arches and long sections.
The flue gas probe was factory installed in the box of the exhaust gas fan. Before starting, it is
necessary to check whether all elements are in place after transport, because the boiler will not
operate without the probe being properly installed. The required chimney draft is 12Pa.
70
Radijator Inženjering d.o.o, 36000 Kraljevo, Živojina Lazića
- Solunca br.6, Srbija
tel. +381 36 399 140, fax. +381 36 399 150, http://www.radijator.rs
e-mail: [email protected]
Figure 9.2 Installation of flue gas channels and fresh air inlet for combustion
The BIOlux UNI 20 boiler operates under forced draft conditions with one fan, but the rules
for the selection of a chimney should be respected as if it was intended for the boiler with a mild
sub-pressure in the firebox working on another fuel type, such as fuel oil. The chimney cross
section should be 130mm, otherwise it may cause problems in the process of operation.
It is recommended for the chimney diameter to be larger than the diameter of a flue outlet.
Arches should be avoided if possible; if not, the maximum number of arches should be 2. It is
desirable to isolate the flue gas channel running from a boiler to a chimney, particularly if there
are arches and long sections.
The flue gas probe was factory installed in the box of the exhaust gas fan. Before starting, it is
necessary to check whether all elements are in place after transport, because the boiler will not
operate without the probe being properly installed. The required chimney draft is 12Pa.
70
Radijator Inženjering d.o.o, 36000 Kraljevo, Živojina Lazića
- Solunca br.6, Srbija
tel. +381 36 399 140, fax. +381 36 399 150, http://www.radijator.rs
e-mail: [email protected]
Figure 9.2 Installation of flue gas channels and fresh air inlet for combustion
The BIOlux UNI 20 boiler operates under forced draft conditions with one fan, but the rules
for the selection of a chimney should be respected as if it was intended for the boiler with a mild
sub-pressure in the firebox working on another fuel type, such as fuel oil. The chimney cross
section should be 130mm, otherwise it may cause problems in the process of operation.
It is recommended for the chimney diameter to be larger than the diameter of a flue outlet.
Arches should be avoided if possible; if not, the maximum number of arches should be 2. It is
desirable to isolate the flue gas channel running from a boiler to a chimney, particularly if there
are arches and long sections.
The flue gas probe was factory installed in the box of the exhaust gas fan. Before starting, it is
necessary to check whether all elements are in place after transport, because the boiler will not
operate without the probe being properly installed. The required chimney draft is 12Pa.