REGULATION INSTRUCTIONS
34
PARAMETER P10 – MINIMUM FAN SPEED SETTING
(not applicable)
PARAMETER
P11
–
MAXIMUM
FAN
SPEED
SETTING
(not applicable)
PARAMETER P12 – MINIMUM FAN SPEED SETTING (CENTRAL
HEATING)
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between: min = 33 Hz ; max = 133 Hz.
The default value is adjusted according to the output set in parameter
P00.
7. Press and release button ‘S’ to confirm. The parameter number
(P12) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
PARAMETER
P13
–
MAXIMUM FAN SPEED SETTING (CENTRAL
HEATING)
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between: min = value of parameter P12 ; max = 203 Hz.
The default value is adjusted according to the output set in parameter
P00.
7. Press and release button ‘S’ to confirm. The parameter number
(P13) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
168
P 13
40
P 12
168
P 11
40
P 10