2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P23
DISABLEMENT OF DOMESTIC HOT WATER LINE BY
MEANS OF SWITCH (ONLY FOR FAST BOILERS)
BY ENABLING THIS PARAMETER IN THE PRESENCE
OF A CONNECTION (FOR EXAMPLE A BOILER CLOCK
OR A TEMPERATURE THERMOSTAT) ON BOILER
CLOCK SWITCH ON THE BOARD, THE REQUEST FOR
BURNER IGNITION ON THE DOMESTIC HOT WATER
LINE WILL BE DISABLED UPON BOILER CLOCK
SWITCH CLOSURE.
EXAMPLE 1:
WITH THE BOILER CLOCK SWITCH
OPEN, UPON THE REQUEST FOR DOMESTIC HOT
WATER, THE FLOW SWITCH AND THE BOILER WILL
TURN ON.
EXAMPLE 2:
WITH THE BOILER CLOCK SWITCH
CLOSE, UPON THE REQUEST FOR DOMESTIC HOT
WATER, THE FLOW SWITCH AND THE BOILER WILL
NOT TURN ON.
0 - 1
0 = DISABLED
(SET BY DEFAULT)
1 = ENABLED
P24
ACTIVATION OF THE AUXILIARY RELAY ON THE
“SVZ” P.C.B. (SEE CHAPTER: OPTIONAL ELECTRICAL
CONNECTIONS)
THROUGH THIS PARAMETER IT IS POSSIBLE TO
MANAGE THE TYPE OF FUNCTIONING OF THE
AUXILIARY RELAY ON THE “SVZ” P.C.B. (CLAMP M4,
PIN 5-6).
WHEN THE VALUE OF THE PARAMETER IS SET TO ‘3’,
THE ENABLING OR DISABLING OF THE AUXILIARY
RELAY IS GIVEN BY THE “TP” CONTACT (SEE
CHAPTER: OPTIONAL ELECTRICAL CONNECTIONS).
WHEN THE “TP” CONTACT IS OPEN, THE RELAY
STAYS ENERGIZED (WORKING RECIRCULATION
PUMP) WHILE WHEN THE “TP” CONTACT IS CLOSED,
THE RELAY IS DE-ENERGIZED (NOT WORKING
RECIRCULATION PUMP).
0 - 4
0 = DISABLED (SET BY DEFAULT)
1 = HEATING CIRCUIT BOOSTER PUMP
2 = D.H.W. BOOSTER PUMP
3 = RECIRCULATION PUMP
4 = REMOTE LED FOR SIGNALLING BOILER
BLOCK
(SEE CHAPTER: OPTIONAL ELECTRICAL
CONNECTIONS)