2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P04
HEATING RUN-UP
THROUGH THIS PARAMETER YOU CAN SET THE
TIME, DURING START-UP PHASE, NECESSARY FOR
THE BOILER TO REACH THE MAXIMUM SET POWER
(ON THE HEATING SIDE).
00 - 04
00 = (DISABLED)
01 = 50 SECONDS
02 = 100 SECONDS
03 = 200 SECONDS
(SET BY DEFAULT)
04 = 400 SECONDS
P05
ANTI-WATER HAMMER SELECTION
ONCE THIS FUNCTION IS ENABLED, THE DHW
CONTACT WILL BE DELAYED FOR A TIME EQUAL TO
THE SET VALUE.
00 - 20
00 = DISABLED
01 - 20 = THE VALUE IS EXPRESSED IN
SECONDS
P06
DOMESTIC CIRCUIT PRESERVATION FUNCTION
(ONLY FOR ISTANTANEOUS BOILERS)
THROUGH THIS PARAMETER YOU CAN PRESERVE
THE CIRCULATOR THE DIVERTER VALVE IN
DOMESTIC POSITION FOR A PERIOD OF TIME EQUAL
TO THE POST-CIRCULATION (SEE PARAMETER P09),
SO AS TO MAINTAIN THE SECONDARY EXCHANGER
HOT.
00 - 01
00 = DISABLED
(SET BY DEFAULT)
01 = ENABLED
P07
HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE
MINIMUM TIME FOR WHICH THE BURNER WILL BE
TURNED OFF ONCE THE HEATING TEMPERATURE
REACHED THE USER SET TEMPERATURE.
00 - 90
VALUE EXPRESSED IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 36 X 5 = 180 SECONDS)
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE
PUMP DURATION OF OPERATION DURING HEATING
CYCLE, AFTER THE MAIN BURNER TURNS OFF DUE
TO THE ENVIRONMENT THERMOSTAT.
00 - 90
VALUE EXPRESSED IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 36 X 5 = 180 SECONDS)
P09
POST-CIRCULATION DOMESTIC / BOILER TIMING
THROUGH THIS PARAMETER YOU CAN SET THE
PUMP OPERATION DURATION ON THE DOMESTIC
CIRCUIT, AFTER THE TAP IS CLOSED.
00 - 90
VALUE EXPRESSED IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 24 X 5 = 120 SECONDS)