2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
(CHANGE THE PARAMETER VALUE ON BOTH CONTROL PANELS,
MASTER AND SLAVE, PLEASE SEE CHAPTER "PARAMETER ACCESS
AND PROGRAMMING").
VALUE
SET FOR
PARAMETER
P10 - 255
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P15
ANTI-LEGIONELLA FUNCTION
(ONLY FOR THE VERSION WITH REMOTE BOILER SUPPLY SYSTEM).
THROUGH THIS PARAMETER YOU CAN ACTIVATE/DEACTIVATE
“ANTI LEGIONELLA” HEAT TREATMENT OF THE ACCUMULATION
BOILER. EVERY 7 DAYS THE WATER TEMPERATURE INSIDE
THE ACCUMULATION BOILER IS HEATED BEYOND 60 °C THUS
GENERATING A BURNING HAZARD. KEEP UNDER CONTROL SUCH
DOMESTIC HOT WATER TREATMENT (AND INFORM THE USERS)
TO AVOID UNFORESEEABLE DAMAGES TO PERSONS, ANIMALS,
PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED AT
THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS.
0 - 1
0 = DISABLED
1 = ENABLED (PRE-SET BY
DEFAULT)