2. FIRST START-UP
SUPPOR
T
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P04
HEATING RUN-UP
THROUGH THIS PARAMETER YOU CAN SET THE TIME, DURING
START-UP PHASE, NECESSARY FOR THE BOILER TO REACH THE
MAXIMUM SET POWER (IN HEATING).
0 - 5
0 = (DISABLED)
1 = 50 SECONDS
(SET BY DEFAULT)
2 = 100 SECONDS
3 = 200 SECONDS
4 = 400 SECONDS
5 = 600 SECONDS
P05
TIME DURING THE PRIMARY START-UP OF A SINGLE UNIT
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO SET THE TIME
DURING WHICH A SINGLE UNIT BECOMES PRIMARY DURING THE
START-UP, AFTER WHICH THE AUTOMATIC REVERSAL WITH THE
OTHER UNIT OCCURS.
0 - 255
THE VALUE IS EXPRESSED IN
HOURS
(PRE-SET TO 50 HOURS)
P06
TURN OFF OF A SINGLE UNIT
1 - 3
1 = START ONLY MASTER
2 = START ONLY SLAVE
3 = BOTH TURNED ON
P07
HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM TIME FOR
WHICH THE BURNER WILL BE TURNED OFF ONCE THE HEATING
TEMPERATURE REACHED THE USER SET TEMPERATURE.
0 - 90
VALUE EXPRESSED IN MULTIPLES
OF 5 SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE PUMP DURATION
OF OPERATION DURING HEATING CYCLE, AFTER THE MAIN
BURNER TURNS OFF DUE TO THE ENVIRONMENT THERMOSTAT.
0 - 90
VALUE EXPRESSED IN MULTIPLES
OF 5 SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P09
POST-CIRCULATION DOMESTIC / BOILER TIMING
(ONLY FOR THE VERSION WITH REMOTE BOILER SUPPLY SYSTEM).
THROUGH THIS PARAMETER YOU CAN SET THE PUMP OPERATION
DURATION ON THE DOMESTIC CIRCUIT, AFTER THE TAP IS CLOSED.
0 - 90
VALUE EXPRESSED IN MULTIPLES
OF 5 SECONDS
(PRE-SET AT 18 X 5 = 90 SECONDS)