5.0
Troubleshooting Guide
NOTICE
Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.
Measure the voltage across
the red wire on the relay
board and ground on the
circuit board. Is there 24 V?
If the heater does not enter High Fire mode, check the following:
Check the power across the green
and black wires of the yellow
control cord. Is there 24 V?
Yes
Repair or replace the faulty
wiring or thermostat.
Yes
The valve is
faulty and must
be replaced.
The high fire relay is faulty
and must be replaced.
No
No
NOTE:
To confirm that the heater is not in high fire
mode, check the manifold pressure. If it is 3.5” (natural
gas) or 10” (propane), the indicator light is faulty and
should be replaced. If approximately 2.0” to 2.5”
(natural gas) or 5.0” to 6.5” (propane), the heater is in low
fire mode and the troubleshooting steps described here
should be followed.
Check to make sure gas pressure is within minimum and
maximum inputs, as indicated on the heater’s rating plate.
Is gas pressure OK?
Were the gas lines purged of air?
Is the heater properly
grounded? Is the heater’s
polarity correct?
With micro-ammeter, check amperage
at flame rod (or pins on circuit board).
Is it greater than 1.0
µ
A (micro-amp)?
Check to make sure flame
sensor wire is OK and then
replace circuit.
Sensing rod is faulty or flame is weak.
Check to make sure heater is operating
at proper gas pressure as indicated on the
heater’s rating plate and then, if needed,
replace sensing rod.
Replace gas valve.
Yes
Correct problem.
Correct problem.
No
No
Yes
Yes
No
Yes
Purge gas line.
No