2920 7101 22
91
Instruction book
Compressor specification
I(1)
Max Fuse
(1)
I(2)
Max Fuse
(2)
Type
gL/gG
gL/gG
A1
30kW
380 60 69 80 76 100
A2
30kW
380 60 69 80 76 100
X 30kW 380 60 69 80 -
-
IEC approval
Compressor specification
I(1)
Max Fuse
(1)
I(2)
Max Fuse
(2)
Type
gL/gG
gL/gG
V Hz A A A A
A1 37kW 230 50 148 160 157 200
A2 37kW 230 50 148 160 157 200
X 37kW 230 50 148 160 -
-
A2 37kW 220 60 154 200 165 200
X 37kW 220 60 154 200 -
-
A1 37kW 230 60 149 160 160 200
X 37kW 230 60 149 160 -
-
A1
37kW
400 50 85 100 91 100
A2
37kW
400 50 85 100 91 100
X 37kW 400 50 85 100 -
-
A1
37kW
440 60 75 100 82 100
A2
37kW
440 60 75 100 82 100
X 37kW 440 60 75 100 -
-
A1
37kW
380 60 89 100 96 125
A2
37kW
380 60 89 100 96 125
X 37kW 380 60 89 100 -
-
IEC approval
Compressor specification
I(1)
Max Fuse
(1)
I(2)
Max Fuse
(2)
Type
gL/gG
gL/gG
V Hz A A A A
A1 45kW 230 50 179 200 188 200
A2 45kW 230 50 179 200 188 200
X 45kW 230 50 179 200 -
-
A2 45kW 220 60 186 200 197 224
X 45kW 220 60 186 200 -
-
A1 45kW 230 60 180 200 190 224
X 45kW 230 60 180 200 -
-
A1 45kW 400 50 103 125 109 125