Installation method C according table B.52.1.
Single-core or multi-core cable on a wooden wall
Maximum allowed current in function of the ambient temperature for installation method C
Ambient temperature
Cable section
30 °C
40 °C
45 °C
50 °C
55 °C
4 mm²
< 32 A
< 28 A
< 25 A
< 23 A
< 20 A
6 mm²
< 41 A
< 36 A
< 32 A
< 29 A
< 25 A
10 mm²
< 57 A
< 50 A
< 45 A
< 40 A
< 35 A
16 mm²
< 76 A
< 66 A
< 60 A
< 54 A
< 46 A
25 mm²
< 96 A
< 84 A
< 76 A
< 68 A
< 59 A
35 mm²
< 119 A
< 104 A
< 94 A
< 84 A
< 73 A
50 mm²
< 144 A
< 125 A
< 114 A
< 102 A
< 88 A
70 mm²
< 184 A
< 160 A
< 145 A
< 131 A
< 112 A
95 mm²
< 223 A
< 194 A
< 176 A
< 158 A
< 136 A
120 mm²
< 259 A
< 225 A
< 205 A
< 184 A
< 158 A
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method
F,conductor temperature 70°C
Ambient temperature
Cable section
30 °C
40 °C
45 °C
50 °C
55 °C
25 mm²
< 110 A
< 96 A
< 87 A
< 78 A
< 67 A
35 mm²
< 137 A
< 119 A
< 108 A
< 97 A
< 84 A
50 mm²
< 167 A
< 145 A
< 132 A
< 119 A
< 102 A
70 mm²
< 216 A
< 188 A
< 171 A
< 153 A
< 132 A
95 mm²
< 264 A
< 230 A
< 209 A
< 187 A
< 161 A
120 mm²
< 308 A
< 268 A
< 243 A
< 219 A
< 188 A
150 mm²
< 356 A
< 310 A
< 281 A
< 253 A
< 217 A
185 mm²
< 409 A
< 356 A
< 323 A
< 290 A
< 249 A
240 mm²
< 485 A
< 422 A
< 383 A
< 344 A
< 296 A
Instruction book
96
2920 7101 24
Содержание QGS 90
Страница 2: ......
Страница 19: ...Electric cubicle Y D typical example Instruction book 2920 7101 24 17...
Страница 21: ...The drawings are on the USB supplied with your machine Instruction book 2920 7101 24 19...
Страница 132: ......
Страница 133: ......
Страница 134: ...No 2920 7101 24 2021 08 Printed in Belgium Performance You Demand Reliability You Trust www quincycompressor com...