Term
Explanation
Minimum stop
time
Once the compressor has automatically stopped, it will remain stopped for the minimum
stop time, whatever happens with the net air pressure. Consult your supplier if a setting
lower than 20 seconds is required.
Unloading/
Loading pressure
The regulator does not accept illogical settings, e.g. if the unloading pressure is
programmed at 7.0 bar(e) (101 psi(g)), the maximum limit for the loading pressure
changes to 6.9 bar(e) (100 psi(g)). The recommended minimum pressure difference
between loading and unloading is 0.6 bar (9 psi(g)).