7
Problem solving
Warnings
•
Before starting any maintenance or repairs, close the air outlet valve and press the
test button on top of the electronic water drain to depressurise the air system.
•
Apply all relevant instructions in section
Safety precautions during maintenance or
Faults and remedies
Condition
Fault
Remedy
Pressure dew point too high
Air inlet temperature too high
Check and correct. If necessary,
install a pre-cooler
Ambient temperature too high
Check and correct. If necessary,
draw cooling air via a duct from a
cooler place or relocate the
dryer.
Air inlet pressure too low
Increase inlet pressure
Dryer capacity exceeded
Reduce air flow
Shortage of refrigerant
Have circuit checked for leaks
and have the refrigerant circuit
recharged
Condition
Fault
Remedy
Condenser pressure too high or too
low
Fan control switch out of order
Replace
Fan or fan motor out of order
Check fan/fan motor
Ambient temperature too high
Check and correct. If necessary,
draw cooling air via a duct from a
cooler place or relocate the
dryer.
Condenser externally clogged
Clean condenser
Condition
Fault
Remedy
Compressor stops or does not start Electric power supply to compressor
is interrupted
Check and correct as necessary
Thermic protection of refrigerant
compressor motor has tripped
Motor will restart when motor
windings have cooled down
On three-phase units, phase
sequence relay fault indication
Reverse two incoming electric
lines.
Instruction book
2920 7103 90
53
Содержание QED-250
Страница 2: ......
Страница 40: ...4 Installation 4 1 Dimension drawings QED 250 and QED 300 dimension drawing Instruction book 38 2920 7103 90...
Страница 42: ...4 2 Installation proposal Installation proposal QED 250 and QED 300 Instruction book 40 2920 7103 90...
Страница 43: ...Installation proposal QED 350 up to QED 600 Text on drawings Instruction book 2920 7103 90 41...
Страница 64: ......
Страница 65: ......