INSTALLATION

ELECTRIC CONNECTIONS

The instrument meets EMC standards (electromagnetic compatibility) however correct installation is fundamental in order 

not to compromise its performance as well as operation of the instruments found nearby. 

For this reason, the instrument’s cables must be at least:  

• 1 m away from cables that carry radio signals (except for SSB radio transmitters).

• 2 m away from cables that carry SSB radio transmitter radio signals.

Follow the rules given below when doing the electrical work for the instrument: 

•  Use the supplied wire or an UTP CAT5 patch-cord to connect the data interface (CANH and CANL signals) and instru-

ment power supply.

•  The data cable cannot be more than 100 meters long.

Two RJ45 sockets for connecting the display to the battery charger and to the termination connector are present on the 

back of the instrument.

RDS 1562

SBC NRG+ HIGH/ MEDIUM POWER

CONNECTION DIAGRAM FIG.1

TERMINATION

CONNECTOR

Always connect the RDS 1562 remote display to the CAN OUT port of the battery charger.

F

The display is powered via the CAN OUT socket of the battery charger. Even in case the battery charger witn one o more 

battery groups turns off, the RDS 1562 will continue displaying the output terminal voltage of the battery charger, if “monitor” 

mode is activates, as it is powered by the battery group connected to the MASTER output (the needed current to power 

the RDS 1562 is 50mA).

Содержание RDS 1562

Страница 1: ...RDS 1562 V Master V Slave 1 V Slave 2 IT Out Status ENTER Manuale di installazione ed uso PANNELLO REMOTO RDS 1562 Manual for use and installation REMOTE DISPLAY RDS 1562 IT EN High Quality Nautical...

Страница 2: ......

Страница 3: ...saggi di avvertimento messaggi di stato Pag 16 GESTIONE PROBLEMI segnalazione problemi gestione problemi dello strumento Pag 17 DATI TECNICI Pag 18 CHARACTERISTICS AND INSTALLATION installing the inst...

Страница 4: ...cazioni da diporto Non consentito un utilizzo differente senza autorizzazione scritta da parte della societ Quick Il pannello remoto RDS 1562 Quick stato progettato per gli scopi descritti in questo m...

Страница 5: ...lsiasi apparato radiotrasmittente escluso SSB 2 m da qualsiasi apparato radiotrasmittente SSB 2 m dal percorso del fascio radar INSTALLAZIONE A PANNELLO Dopo aver scelto dove posizionare lo strumento...

Страница 6: ...i CANH e CANL e alimentazione dello strumento il cavo in dotazione o una patchcord UTP CAT5 La lunghezza massima totale del cavo dati deve essere non superiore a 100 metri Sul retro dello strumento so...

Страница 7: ...BUS CARICABATTERIE IN PARALLELO Di seguito si riporta un esempio di collegamento della rete per caricabatterie collegati in parallelo modalit di ripartizione di corrente SBC NRG HI POWER SBC NRG HI P...

Страница 8: ...icabatterie serie NRG MEDIUM o HIGH Indicazione relativa alla misura della tensione sui terminali di uscita del caricabatterie Il simbolo che compare in questa zona indica che vi sono pi messaggi di s...

Страница 9: ...ILENZ Permette l abilitazione o la disabilitazione della modalit silenziosa RESET Permette il reset del caricabatteria CONFIG RDS Permette l impostazione dei parametri del pannello remoto RDS 1562 USC...

Страница 10: ...econdario g G R U P P O C A N p P G R U P P O A q SBC 1100 NRG FR PRIORIT 2 SBC 750 NRG FR GRUPPO A GRUPPO B GRUPPO U RETE CAN UNIT IN PARALLELO KTB4 RDS 1562 KTB4 RDS 1562 INTERFACCIA GSM TERMINALE L...

Страница 11: ...e essere la stessa in tutti i caricabatterie Disabilitato Impostazione di fabbrica Abilitato Uscita SOGLIA DI FLOAT MASSIMA CORRENTE DI USCITA SOGLIA DI FLOAT Questa funzione permette l impostazione d...

Страница 12: ...trumento la stessa priorit del caricabatterie NRG ad esso collegato Accertarsi di assegnare allo strumento la stessa priorit del caricabatterie di cui si vogliono visualizzare i dati PRIORIT 1 Imposta...

Страница 13: ...ette l abilitazione o la disabilitazione della segnalazione acustica beep veloce in presenza di errori a reset manuale La segnalazione acustica pu essere tacitata mantenendo premuti contemporaneamente...

Страница 14: ...un valore superiore a 207 Vac mod SBC 1450 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR o 108 Vac mod SBC 600 NRG FR SBC 700 NRG FR SBC 750 NRG FR SBC 950 NRG FR SBC 1100 NRG FR SBC 1200 NRG FR AC assente L...

Страница 15: ...1200 NRG FR o 29 6 Vdc mod SBC 750 NRG FR SBC 950 NRG FR SBC 1450 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR La segnalazione scompare non appena la tensione si riporta ad un valore minore uguale a 14 8 V...

Страница 16: ...o in cui sia riscontrato un problema al checksum della mamoria flash compare la seguente segnalazione Mancato collegamento con il caricabatteria La seguente segnalazione compare se l impostazione effe...

Страница 17: ...RALI Dimensioni L x A x P 116 5 x 77 2 x 27 2 mm Peso 105 g Interfaccia di comunicazione CAN bus con trasceiver differenziale Standard EMC EN60945 FCC TITLE 47 PART 15 SUBPART B CLASS B 1 Lo strumento...

Страница 18: ...use are not permitted without written authorization from the company Quick The Quick RDS 1562 remote display has been designed for the purposes and tasks outlined in this User s Manual Quick shall no...

Страница 19: ...m away from any SSB radio transmitters 2 m away from radar beams PANEL INSTALLATION After selecting the area where the instrument is to be installed perform the steps given below Place the drilling te...

Страница 20: ...the data interface CANH and CANL signals and instru ment power supply The data cable cannot be more than 100 meters long Two RJ45 sockets for connecting the display to the battery charger and to the t...

Страница 21: ...N TO THE BATTERY CHARGER CAN BUS NETWORK IN PARALLEL Here following is an example of network connection for battery chargers connected in parallel current sharing mode SBC NRG HI POWER SBC NRG HI POWE...

Страница 22: ...or HIGH series battery chargers manual Information concerning the voltage measured on the output terminals of battery charger The symbol that is shown in this area means that there are several system...

Страница 23: ...isabling of silent mode RESET Allows the reset of the battery charger CONFIG RDS Allows the setting of the parameters of the RDS 1562 remote panel EXIT Exits the menu The programmable functions inside...

Страница 24: ...GROUP CONFIGURATION A diagram is given below showing an example of a possible network BATTERY TYPE This function displays the type of battery selected on the battery charger Open liquid Sealed liquid...

Страница 25: ...t sharing mode the same option must be selected on all the battery chargers Disable Factory setting Enable Exit FLOAT THRESHOLD MAXIMUM OUTPUT CURRENT THR FLOAT This function sets the value in the for...

Страница 26: ...ute to the instrument the same priority of the NRG battery charger connected to it Ensure that you assign to the instrument the same priority of the battery charger of which you want to display the da...

Страница 27: ...N ERRORS It allows to enable or disable the acoustic signaling fast beep in case of manual reset errors The acoustic signaling can be silenced by keeping the UP DOWN buttons pressed simultaneously DIS...

Страница 28: ...than 207 Vac mod SBC 1450 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR or 108 Vac mod SBC 600 NRG FR SBC 700 NRG FR SBC 750 NRG FR SBC 950 NRG FR SBC 1100 NRG FR SBC 1200 NRG FR AC fail The AC mains voltage...

Страница 29: ...50 NRG HR SBC 1950 NRG HR SBC 2450 NRG HR Batt 2 lo The battery s or battery bank s voltage measured on the SLAVE2 output terminal is lower than 11 Vdc mod SBC 600 NRG FR SBC 700 NRG FR SBC 1100 NRG F...

Страница 30: ...appear if there is a problem with the flash memory checksum Failure connection with the battery charger The following signaling appears if The group or priority setting carried out in the CONFIG RDS...

Страница 31: ...ERALS Dimensions W x H x D 116 5 x 77 2 x 27 2 mm 4 19 32 x 3 1 32 x 1 3 4 Weight 105 g Comunication interface CAN bus with differential trasceiver EMC Standard EN60945 FCC TITLE 47 PART 15 SUBPART B...

Страница 32: ...32 RDS 1562 IT EN REV001A 116 5 4 19 32 77 2 3 1 32 102 3 4 1 32 27 2 1 3 4 7 1 7 64 RDS 1562 DIMENSIONI DIMENSIONS mm inch...

Страница 33: ...33 33 RDS 1562 IT EN REV001A NOTES...

Страница 34: ...NOTES...

Страница 35: ......

Страница 36: ...EMOTE DISPLAY Quick S p A Via Piangipane 120 A 48124 Piangipane RA ITALY Tel 39 0544 415061 Fax 39 0544 415047 www quickitaly com R001a Codice e numero seriale del prodotto Product code and serial num...

Отзывы: