15
04.10.2021
20210927 QC-PC-PID-01-Bedienungsanleitung engl.
KP
Proportional part of the PID control
TN
Integral part of the PID control
0 switches off the integral part
TV
Differential component of the PID control 0 switches off the differential part
The controller can thus be set to pure P, PI, PD or PID control characteristic.
PM
shows the set voltage limit as a percentage of the input voltage
T1
freely selectable temperature value 1
T2
freely selectable temperature value 2
changes the setpoint (
TAR-TEMP
) to the temperature value 1
T1
changes the setpoint (
TAR-TEMP
) to the temperature value 2
T2
ACT-TEMP
(actual temperature)
shows the actual temperature measured at the sensor
TAR-TEMP
(target temperature)
shows the set target temperature
TEC-CUR
shows the current flow through the connected element
TEC-V
shows the actual output-voltage
AUTO ON/OFF
shows the status of the autostart function
switches the
Autostart
function ON or OFF.
In the autostart-ON mode, the controller starts immediately after the supply voltage is
switched on, if it was previously switched off with the output switched on.
In autostart-OFF mode, the controller always starts with the output switched off.
Key Function: Stop output
Display Function: Output is ON.
Key Function: Starts output
Display Function: Output is OFF.
jumps back to the MONITOR-menu
jumps to the
PA
rameter
SET MENU
. The values
KP
,
TN
and
TV
can be stored here.