13. Flush Shutter DC Calibration
Automatic calibration
Automatic calibration is a process during which the Flush Shutter DC learns the position of the
limit switches.
Shutter positioning calibration
(par. 71 set to 0)
•
Calibration through main gateway (hub) UI
1) Include the device into the Z-wave network according to the instructions for inclusion.
2) Set the parameter 78 (Forced Flush Shutter DC calibration) value to 1.
3) Flush Shutter DC performs the calibration process, completing full cycle - up, down and
up again.
4) Set the parameter 78 (Forced Flush Shutter DC calibration) value to 0.
Slates tilting position calibration
(par. 71 set to 1)
When enabling venetian blind mode, position calibration for slats titling must be done. After
doing this, position and angle of slates can be set. By default, full turn time for slates is set to
1.5s. This value can be changed with parameter 72.
1) Include and make device calibration according to secti
on ‘Shutter positioning calibration’.
2) Set parameter 71 to 1 ‘Venetian blinds’.
3) Exclude the device (without reset!).
4) Include the device.
5) After device inclusion beside main Shutter widget, another widget for slates control will appear
on UI.
Содержание FLUSH SHUTTER DC
Страница 3: ...EN 3 18 Warning 58 19 Regulations 58...
Страница 16: ...EN 16 4 Package Contents Flush Shutter DC Device Installation Manual...
Страница 23: ...EN 23 After Qubino installation...
Страница 29: ...EN 29 Step 2 Turn the fuse OFF Step 3 Connect the temperature sensor as shown below...
Страница 30: ...EN 30 Step 4 Place the temperature sensor in the switch box Step 5 Turn the fuse ON...
Страница 31: ...EN 31 Step 6 Re include the device to your network...
Страница 32: ...EN 32 Step 7 Start using the temperature sensor in connection with your device...