DXi6500 and DXi6700 Specifications
19
DXi6500 and DXi6700 Site Planning Guide
Environmental
Specifications
Table 11
provides various DXi6500 and DXi6700 environmental specifications.
Table 11 Environmental
Specifications
Climatic Environment
Temperature
Operating
10° to 35°C (50° to 95°F) up to 3048m (10,000 ft)
Shipping and storage
–20° to 60°C (–4° to 140°F) up 12,000m (39,370 ft)
Relative humidity
Operating
20% to 80% (non-condensing)
Shipping and storage
5% to 95% (non-condensing)
Altitude
Operating
–30m to 3048 m (–100 to 10,000 ft)
Shipping and storage
–30m to 12,000 m (–100 to 39,370 ft)
Vibration and Shock
Operational Shock
Peak Acceleration
3G
Duration
8 milliseconds
Wave Shape
½ Sine
Operational Vibration
Mode
Swept frequency
Frequency Range
20Hz–300Hz
Amplitude
0.25G
Rate/Duration
0.75 octaves/minute
Application
X, Y, and Z axes
Shipping and Storage
Mode
Random Vibration
Frequency Range
4Hz–300Hz
Amplitude
0.96 Grms
Rate/Duration
(PSD can be provided) 30 minutes X, Y, Z axes
Acoustic
Acoustic output
Operating
< 67 dBA at 1 meter, room temperature (20C)
Agency Approvals
Safety
IEC 60950-1 (ed. 1), CSA 60950-1-03/UL 60950-1 1st Edition
Emissions
EN55022 Class A, FCC Part 15 Class A, ICES-003 Class A, VCCI Class A, CISPR 22 Class A,
CNS13438 Class A, KN22 Class A