Section 4 - Installation
Form QTC4-NM2
Issue date: 05/12/2023
Dual point wiring
Figure 19 -
Dual point power wiring
LD18589a
115V/60Hz
220V/50Hz
L N
PE/GND
FAN
CONTACTORS
TERMINAL BLOCK
CIRCUIT BREAKER - OPT
NON-FUSED DISCONNECT SW. - OPT
SYSTEM 2
LINE
REACTOR
POWER
ASSEMBLY
SYSTEM 2
UNIT CONTROLS
EVAPORATOR AND COMPRESSOR
HEATERS
VSD COOLING PUMP
AND FAN
FAN
CONTACTORS
STANDARD
CONTROL
TRANSFORMER
LINE
REACTOR
TERMINAL BLOCK
CIRCUIT BREAKER - OPT
NON-FUSED DISCONNECT SW. - OPT
SYSTEM 1
POWER
ASSEMBLY
SYSTEM 1
COMPRESSOR SYSTEM 1
COMPRESSOR SYSTEM 2
L1 L2 L3
PE/GND
PE/GND
L1 L2 L3
380~415-3-50
460-3-60
380~415-3-50
460-3-60
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
FIELD PROVIDED
UNIT POWER
SUPPLY
FIELD PROVIDED
UNIT POWER
SUPPLY
UNIT MOUNTED ELECTRONICS
WATER BOX
HEATER
KIT
Minimum circuit ampacity (MCA), mini
-
mum/maximum fuse size, and minimum/
maximum circuit breaker size vary on
chillers based upon model and options
ordered. Consult YorkWorks or the chiller
data plate for electrical data on a specific
chiller.
Note 1:
Dashed line represents customer wiring.
Voltage utilization range
Rated voltage
Utilization range
200/60/3
180–220
230/60/3
208–254
380/60/3
342–418
400/60/3
360–440
460/60/3
414–508
575/60/3
520–635
400/50/3
360–440
Содержание QTC40160
Страница 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Страница 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Страница 100: ...Quantech 100 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Страница 158: ...Quantech 158 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Страница 187: ...Quantech 187 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...